36
F
E
D
C
Safety assembly supplied
C
Pressure gauge
D
Connection G¾
E
Quick-action air vent valve
F
Safety valve
1.
Connect the secondary lines to the
heat pump:
!
Please note
Ensure hydraulic connections
are tight.
Ensure the diaphragm grom-
mets at the pipe entries are
seated correctly. Seal with
sealing tape if necessary: See
chapter "Assembly and seal-
ing faces to note".
2.
Fit the safety assembly supplied:
Either to an on-site line in the heating
water return or to the secondary cir-
cuit connection set (accessory).
Connection set installation
instructions
3.
Fill and vent the secondary circuit.
4.
Thermally insulate pipes inside the
building.
Note
■ With underfloor heating circuits, install
a temperature limiter to restrict the
maximum temperature in underfloor
heating systems: See chapter "Con-
necting a temperature limiter to restrict
the maximum temperature in under-
floor heating systems".
■ Ensure minimum flow rate is main-
tained, for example by means of an
overflow valve: See "Specification".
■ The secondary circuit must be equip-
ped on site with an expansion vessel.
Installation sequence
Connecting the secondary circuit
(cont.)
5546 699 GB
Содержание AWT-AC 241.A04
Страница 19: ...19 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 20: ...20 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5546 699 GB...
Страница 21: ...21 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5546 699 GB Service...
Страница 104: ...104 0010 0009 0007 0002 0004 0008 0001 0005 0003 0006 Parts lists internal unit Casing internal unit cont 5546 699 GB...
Страница 165: ...165 5546 699 GB...
Страница 166: ...166 5546 699 GB...
Страница 167: ...167 5546 699 GB...