64
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ventilation
Parameters
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Vitovent 300-F
"2"
Vitovent 200-C
Other enabling settings, if applicable:
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
"Enable reheater bank hydraulic 7D02"
"1"
"Enable humidity sensor 7D05"
"1"
"Enable CO2 sensor 7D06"
"1"
If necessary, set values:
"Ventilation"
Ó
"Set extract air temperature 7D08"
(only in conjunction with
Vitovent 300-F)
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Parameters for utilisation of power generated on site
Parameters
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Enable functions for utilisation of power generated on site.
"Photovoltaics"
Ó
"Enable own energy consumptn for set DHW temperature 2
7E10"
"1"
"Enable own energy consumption for DHW heating 7E11"
"1"
"Enable own energy consumptn for heating water buffer cyl.
7E12"
"1"
"Enable own energy consumption for heating 7E13"
"1"
"Enable own energy consumption for cooling 7E15"
"1"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5776 028 GB
Содержание AWT 221.A04
Страница 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Страница 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Страница 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Страница 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Страница 138: ...138 5776 028 GB...
Страница 139: ...139 5776 028 GB...