Recommended power cables:
Rated heating output
4 kW
7 kW
10 kW
13 kW
External unit
(compressor)
230 V~
Cable cross-section
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 4.0 mm
2
3 x 6.0 mm
2
Max. cable length
25 m
25 m
25 m
30 m
Heat pump control unit
(internal unit)
230 V~
3 x 1.5 mm
2
3 x 1.5 mm
2
3 x 1.5 mm
2
3 x 1.5 mm
2
Instantaneous heating
water heater
9 kW (if instal-
led, internal unit)
Cable cross-section
■ 400 V~ (phase symmetri-
cal/asymmetrical)
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
■ 230 V~ (phase asymmet-
rical)
7 x 2.5 mm
2
7 x 2.5 mm
2
7 x 2.5 mm
2
7 x 2.5 mm
2
Max. cable length
25 m
25 m
25 m
25 m
Overview of possible system schemes
The following table provides an overview
of
all
possible system schemes ("Sys-
tem scheme").
Preparing for installation
Requirements of on-site connections
(cont.)
5724 152 GB
Содержание AWS 104
Страница 5: ...5 Certificates Declaration of conformity 119 Keyword index 120 Index Index cont 5724 152 GB...
Страница 86: ...86 Placing the control panel in its service position 4x 1 2 3 Troubleshooting Repairs 5724 152 GB...
Страница 87: ...87 Opening programming unit 3 2 1 2x Troubleshooting Repairs cont 5724 152 GB Service...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5724 152 GB...
Страница 89: ...89 Removing separating plate 1 2 Troubleshooting Repairs cont 5724 152 GB Service...
Страница 98: ...98 101 300 104 231 100 232 230 105 103 103 300 A Parts lists Parts list internal unit cont 5724 152 GB...
Страница 106: ...106 622 614 643 670 642 615 616 637 640 639 669 Parts lists Parts list external unit type AWS AWS AC cont 5724 152 GB...