23
For handling purposes, the heat pump
module can be removed (see
page 89).
!
Please note
Prevent damage to the appliance
during handling.
Never
put weight on the top, front
or side panels of the appliance.
!
Please note
Tilting the compressor at a steep
angle inside the heat pump can
result in appliance damage.
Max. tilting angle 45 °
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Ensure ambient temperatures
between 0 and 35 °C.
!
Please note
Avoid risks of explosion due to
dust, gases and vapours.
Avoid dust, gases and vapours in
the installation room.
!
Please note
Observe the permissible floor
load.
■ Align the appliance horizon-
tally.
If the adjustable feet are used
to compensate for an uneven
floor (max. 10 mm), the pres-
sure load on the feet must be
distributed evenly.
■ The total weight must be con-
sidered (see table).
Total weight
Type
Weight
BW 351.A18
312 kg
BWS 351.A18
307 kg
To prevent the transmission of structure-
borne noise, never site the appliance on
ceilings with wooden joists, e.g. in the
attic.
Minimum room volume (to EN 378)
Type
Minimum spa-
tial volume
BW 351.A18
24 m
3
BWS 351.A18
24 m
3
Preparing for installation
Siting conditions
5546 267 GB
Installation
Содержание 7514659
Страница 30: ...30 Installing the programming unit 2x 3 2 1 Installation sequence Electrical connections 5546 267 GB...
Страница 67: ...67 A Installation sequence Checking diaphragm grommets cont 5546 267 GB Installation...
Страница 84: ...84 Overview of electrical components Type BW 351 A18 D L K H G F E C B A Troubleshooting Repairs 5546 267 GB...
Страница 138: ...138 5546 267 GB...
Страница 139: ...139 5546 267 GB...