81
Coding in the delivered condition
Possible change
31:...
Set speed of the internal circula-
tion pump when operated as boiler
circuit pump in %, specified by the
boiler coding card
31:0
to
31:100
Set speed adjustable from 0 to
100 %
38:0
Status of burner control unit: Op-
erational (no fault)
38:≠0
Status of burner control unit: Fault
"DHW"
Select group
"DHW"
(see page 75).
Coding
Coding in the delivered condition
Possible change
56:0
Set DHW temperature adjustable
from 10 to 60 °C
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Note
Max. value subject to boiler coding
card.
Observe the maximum permissible
DHW temperature.
57:0
Do not adjust
58:0
Without auxiliary function for DHW
heating
58:10
to
58:60
Input of a 2nd set DHW tempera-
ture, adjustable from 10 to 60 °C
(observe coding addresses "56" and
"63" in this group)
5E:0
Do not adjust
5F:0
Do not adjust
65:...
Do not adjust (Information on the
type of diverter valve, specified by
the boiler coding card)
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Above the se-
lected set temperature, DHW re-
heating suppression is active
(DHW heating by the boiler only if
solar energy is insufficient).
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
Observe setting for coding address
"56".
6C:100
Set speed of internal circulation
pump for DHW heating 100 %
6C:0
to
6C:100
Set speed adjustable from 0 to
100 %
6F:...
Max. heating output for DHW heat-
ing in %, specified by boiler coding
card
6F:0
to
6F:100
Max. heating output for DHW heat-
ing adjustable from min. heating out-
put to 100 %
71:0
DHW circulation pump: "ON" ac-
cording to time program
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:0
DHW circulation pump: "ON" ac-
cording to time program
72:1
"OFF" during DHW heating to set
value 2
Code 2
"Boiler"
(cont.)
5773 238 GB
Codes
Содержание 7513244
Страница 11: ...11 8 9 4x 8x 12 10 11 Fig 2 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 12: ...12 13 14 15 Fig 3 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 13: ...13 16 Fig 4 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 14: ...14 sF 17 19 21 20 18 Fig 5 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 15: ...15 24 22 23 Fig 6 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 16: ...16 27 26 25 Fig 7 Preparing for installation Installation preparations cont 5773 238 GB Installation ...
Страница 35: ...35 2x 1 4 2 3 5 Fig 27 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Страница 135: ...135 Parts lists Hydraulic assembly 5773 238 GB Components ...
Страница 146: ...146 0004 0002 0005 0006 0001 0003 Fig 107 Parts lists Miscellaneous 5773 238 GB Components ...