77
Disabling the service menu
The service menu remains active until it
is disabled with
"Terminate service?"
,
or if no operation takes place for 30
minutes.
Setting parameters using the "Sys-
tem scheme" example
To set a parameter, first select the
parameter group and then the parame-
ters.
All parameters are displayed as plain
text. A parameter code is also assigned
to each parameter.
Service menu:
1. Press
OK
+
å
simultaneously for
approx. 4 s
2. Select
"Coding level 1"
3. Select parameter group:
"System
definition"
4. Select parameter:
"System scheme
7000"
5. Set system scheme:
"6"
Alternatively, if the service menu was
already enabled:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
4. Select parameter group:
"System
definition"
5. Select parameter:
"System scheme"
6. Confirm parameter code:
"7000"
7. Set system scheme:
"6"
Required parameters for the heat pump
"Output compressor stage 5030"
The heating output of the heat pump,
subject to type,
must
be selected during
commissioning.
Type AWB/AWB-AC
201.A04
201.A07
201.A10
201.A13
"Output compressor stage
5030"
4 kW
7 kW
10 kW
13 kW
Required parameters for components
connected on site
Detailed explanations of the
parameters
Service instructions for Vitotronic
200 heat pump control unit
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5601 429 GB
Service
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...