37
■ Route LV leads < 42 V and
cables > 42 V/230 V~/400 V~
separately.
■ Strip the insulation from the
cables as close to the terminals
as possible, and bundle tightly
to the corresponding terminals.
■ Secure cables with cable ties.
This ensures that, should there
be an error, for example when
detaching a wire, the wires can-
not drift into the adjacent voltage
area.
!
Please note
The BUS connecting lead for the
internal/external unit (12 V or
43 V) is, in accordance with
safety requirements,
not
a low
voltage cable.
The BUS connecting lead
must
be routed together with the
230 V cables.
Note
To ensure that the control panel can be
placed in the service position (see
page 85), all connections on the con-
trol panel (see page 39) must be made
with flexible cables.
Installation sequence
Electrical connections
(cont.)
5601 429 GB
Installation