Fig. 6: Connection diagram
1 - line L
2 - line N
3 - PE line
4 - fault (alarm)
5 - flush command (flushing)
6 - water exchange ongoing (flushing ongoing)
7 - backflow (fault backflow)
8 - flush command (6–48 V AC/DC)
9 - flowthrough volume (4–20 mA)
10 - 100–240 V AC
The outputs are digital outputs (potencial-free N.O. contacts).
The connectors 4, 6 and 7 are binary outputs which can be evaluated in
an isolated circuit.
Connector 5 is a binary input which can be actuated in an isolated cir-
cuit to carry out a water exchange.
When evaluating the switching contact 6 - water exchange ongoing
(flushing ongoing) -, note the switch-on delay of 2-3 seconds at the
beginning.