background image

5.3. Protections and automatic restarts

Overload

Some loads like motors or pumps draw large inrush currents in a start-up situation. In such circumstances, it is possible that
the start-up current exceeds the over current trip level of the inverter. In this case the AC output voltage will quickly decrease to
limit the output current of the inverter. If the over current trip level is continuously exceeded, the inverter will shut down, wait 30
seconds and then restart.

After 3 restarts, followed by another overload within 30 seconds of restarting, the inverter will shutdown and remain off. The LEDs
will signal shutdown due to overload. To restart the inverter, switch it off and than back on again.

Low battery voltage (adjustable)

The inverter will shut down when the DC input voltage drops below the "Low battery shutdown" parameter. The LEDs will signal
shutdown due to low battery. The inverter will automatically restart, after a minimum delay of 30 seconds, when the battery
voltage has increased above the "Low battery restart" parameter.

After three restarts, followed by another low battery shutdown within 30 seconds of restarting, the inverter will shutdown and
remain off. The LEDs will signal shutdown due to low battery. To restart the inverter, switch it off, and then on again. Alternatively,
recharge the battery. The inverter will automatically restart when the battery voltage has increased for at least 30 seconds above
the "Charge detect" parameter.

See the 

Technical specifications [16]

 chapter for default low battery shutdown and restart levels. The levels can be customized

via the VictronConnect app.

Alternatively, a dynamic low battery cut off can be implemented. For more information, see the 

Dynamic cut off [8]

 chapter.

High battery voltage

The inverter will shut down when the DC input voltage is too high. The LEDs will signal shutdown due to high battery. The inverter
will first wait 30 seconds and will only resume operation once the battery voltage has dropped to an acceptable level.

Check for faulty battery chargers, alternators or solar chargers connected to the battery.

High temperature

The inverter will shut down if it detects a too high internal temperature. The LEDs will signal shutdown due to high temperature.
The inverter will wait 30 seconds and will only resume operation when the temperature has dropped to an acceptable level.

High temperature alarms are generally caused by a too high ambient temperature, often in combination with a high inverter load.
Check if the area the inverter is used in, is well ventilated and perhaps even air-conditioned.

High DC ripple

The inverter will shut down if it detects a too high DC ripple. The LEDs will signal shutdown due to high DC ripple. The inverter
will wait 30 seconds and then resumes operation again. If after 3 restarts, the DC ripple voltage is still too high, the inverter will
shutdown and will not attempt to restart again. To restart the inverter, switch it off and then switch it on again.

High DC ripple is usually caused by loose DC cable connections and/or too thin DC wiring. To clear or prevent ripple alarms,
check the wiring between the battery and the inverter. Check if the wiring is the recommended thickness, that all connections are
tightened correctly and that the fuses and battery isolators are in good working order. For more information on DC ripple see the

Wiring Unlimited book

.

Continuous high DC ripple reduces the life expectancy of the inverter.

5.4. Monitoring via VictronConnect

The VictronConnect app can be used to monitor the inverter.

Phoenix Inverter Smart Manual

Page 14

Operation

Содержание Phoenix Inverter Smart

Страница 1: ...Phoenix Inverter Smart Manual Rev 00 05 2022 ENGLISH...

Страница 2: ...ect settings 7 4 3 1 Dynamic cut off 8 4 4 Programmable relay 9 4 5 Firmware update 9 4 6 Reset settings to default 10 5 Operation 11 5 1 Inverter 11 5 1 1 On Off Push button 11 5 1 2 On off Switch 5k...

Страница 3: ...t is likely that the grounding protection has been damaged the product must be turned off and secured against unintended operation please contact qualified service staff Ensure that the equipment is u...

Страница 4: ...d ECO mode sensitivity level Programmable relay To transfer the load to another AC source The automatic transfer switch For inverters we recommend our Filax2 automatic transfer switch The Filax2 featu...

Страница 5: ...additional VE Direct cable is needed for this 2 6 Remote on off control The inverter can be remotely turned on or off in the following ways Via the VictronConnect app With an optional external switch...

Страница 6: ...0 C humidity 95 non condensing Note that in extreme situations the inverter s case temperature can exceed 70 C Excessive high ambient temperature will result in a reduced service life reduced peak pow...

Страница 7: ...bsite Battery connection procedure Use an insulated box spanner in order to avoid shorting the battery The maximum torque is 11Nm Avoid shorting the battery cables Proceed as follows to connect the ba...

Страница 8: ...annot be accidentally turned back on by another user Inverter control panel If a Phoenix Inverter Control VE Direct panel is used it needs to be connected to the inverter remote connector as is indica...

Страница 9: ...load adjustable the inverter will go back to normal operation mode Once the load drops below a certain level the inverter will go back to ECO mode Below table indicates the default settings and settin...

Страница 10: ...elow graph shows the discharge ratio versus battery voltage curve for the different battery types You can see that the lithium curve LiFePO4 is nearly flat compared to the OPzV and OPzS curve The curv...

Страница 11: ...that it is time to do something charge the battery reduce the load and so forth in order to prevent a power outage Low battery Relay on during normal operation The relay will switch off once there is...

Страница 12: ...following way Navigate to the inverter settings by clicking on the cog symbol in the right top corner Click on the 3 dot symbol in the right top corner Select Reset to defaults from the menu and the s...

Страница 13: ...cut off the supply current completely The switch is located at the bottom right of the inverter next to the battery cable entries 5 1 3 ECO Mode The inverter can be switched to ECO mode via the Victr...

Страница 14: ...than the inverter rating and that if this situation continues the inverter will switch off due to an overload alarm Reduce the AC load The green inverter LED is blinking with a fast double pulse The r...

Страница 15: ...attery voltage alarm The inverter has shut down due to high battery voltage Reduce the DC input voltage check if the battery voltage is correct and if the battery bank is wired correctly Also check if...

Страница 16: ...ee the Dynamic cut off 8 chapter High battery voltage The inverter will shut down when the DC input voltage is too high The LEDs will signal shutdown due to high battery The inverter will first wait 3...

Страница 17: ...ring via a GX device GlobalLink and the VRM portal The inverter can be connected to a GX device like a Cerbo GX or a Color Control GX When connected the GX device will display the inverter on the syst...

Страница 18: ...load power in ECO mode 0 6 1 3 2 1W 0 6 1 3 2 1W 1 5 1 9 2 8W 2 2 3 2W GENERAL Programmable relay DC rating 4A 35V or 1A 60V AC rating 3A 230V Stop start power ECO mode Adjustable via VictronConnect a...

Страница 19: ...9 x 125mm 485 x 219 x 125mm 533 x 285 x 150mm 12V 485 x 285 x 150mm 24 28V 595 x 295 x 160mm 24V 555 x 295 x 160mm 48V STANDARDS Safety EN IEC 60335 1 Emission Immunity EN 55014 1 EN 55014 2 EN IEC 61...

Страница 20: ...7 Appendix 7 1 Connection overview Connections 1600VA model Connections 2000VA model Phoenix Inverter Smart Manual Page 18 Appendix...

Страница 21: ...Connections 3000VA model Phoenix Inverter Smart Manual Page 19 Appendix...

Страница 22: ...ation information floating ground 1600VA and 2000VA models Ground wire G connects the output neutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floa...

Страница 23: ...eutral to ground It must be re positioned to a dummy terminal if a floating output is required When a floating output is obtained the current reading at no load can show an offset of around 100 150mA...

Страница 24: ...0000 Phoenix Inverter 24 1600 230V Smart PIN482160000 Phoenix Inverter 48 1600 230V Smart PIN122200000 Phoenix Inverter 12 2000 230V Smart PIN242200000 Phoenix Inverter 24 2000 230V Smart PIN482200000...

Страница 25: ...0 175 6 5 4 x 46 4 55 87 5 87 5 98 6 2 3 x 32 5 Rev00 Dimensions in mm Dimension Drawing Phoenix Inverter 3000VA Smart PIN122300000 Phoenix Inverter 12 3000 230V Smart D E F C 1 2 3 4 B A 3 2 1 5 C D...

Страница 26: ...87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 3000VA Smart PIN242300000 Phoenix Inverter 24 3000 230V Smart PIN482300000 Phoenix Inverter 48 3000 230V Smart Dimensions in mm D E F C 1...

Страница 27: ...9 6 5 4 x 32 5 55 87 5 87 5 98 6 2 3 x Rev00 Dimension Drawing Phoenix Inverter 5000VA Smart PIN242500000 Phoenix Inverter 24 5000 230V Smart PIN482500000 Phoenix Inverter 48 5000 230V Smart Dimension...

Отзывы: