 Style AQC-U Sprinkler Fitting for Cleanroom Applications / Installation Instructions

IMPORTANT INSTALLATION INFORMATION

• 

The installer shall wear proper cleanroom attire during installation 
of the Victaulic

®

 VicFlex

 Style AQC-U. Contact the building owner 

or their representative to confirm requirements for the specific 
cleanroom application.

• Victaulic

®

 VicFlex

 products shall be installed according to 

current, applicable National Fire Protection Association (NFPA 
13, 13D, 13R, etc.) standards or equivalent standards. Victaulic

®

 

VicFlex

 products are intended to be installed in wet, dry, or 

preaction actuated systems. Deviations from these standards or 
alterations to Victaulic

®

 VicFlex

 products or sprinklers will void 

any Victaulic warranty and will impact system integrity. Installations 
shall meet the provisions of the local authority having jurisdiction 
and local codes, as applicable.

• Victaulic

® 

VicFlex

 Style AQC-U Sprinkler Fittings shall not be 

intermixed with other manufacturer’s flexible sprinkler products.

• 

Refer to the specific Victaulic product submittal for applications 
and listing information. In addition, when installing Victaulic 
FireLock

®

 Automatic Sprinklers with Victaulic

®

 VicFlex

 

Sprinkler Fittings, refer to the I-40 Installation and Maintenance 
Instructions for details on sprinkler installation requirements. 
Submittals and installation instructions can be downloaded at 
victaulic.com.

• 

Size the piping system to provide at least the minimum required 
flow rate for the sprinkler system.

• 

Per NFPA requirements, flush the system to remove foreign 
material. Continue to flush the system until water runs clear.

• 

DO NOT

 install sprinkler system piping through heating ducts.

• 

DO NOT

 connect sprinkler system piping to domestic hot water 

systems.

• 

DO NOT

 install sprinklers and sprinkler fittings where they will 

be exposed to temperatures that exceed the maximum ambient 
temperature rating for the sprinkler and sprinkler fittings.

• 

The flexible hose shall not be bent or fluctuated up-and-down or 
side-to-side when it is pressurized.

• 

Flexible hose and fittings have limited flexibility* and are 
intended only to be installed with bends not less than their 
respective minimum bend radii. DO NOT install flexible hose in 
a straight configuration.

• 

Protect wet piping systems from freezing temperatures.

• 

If construction is altered, refer to applicable standards to determine 
if additional sprinklers are required.

• 

The owner is responsible for maintaining the fire protection system 
in proper operating condition.

• 

For minimum maintenance and inspection requirements, refer to 
NFPA 25 and any other applicable NFPA standards that describe 
the care and maintenance of sprinkler systems. In addition, the 
authority having jurisdiction may have additional maintenance, 
testing, and inspection requirements that shall be followed.

 WARNING

•  Relocation of Victaulic

®

 VicFlex

™ 

products SHALL be performed 

by qualified personnel familiar with the system’s original design 
criteria, sprinkler listings/ approvals, and state and local codes 
(including NFPA 13 standards).

Failure to relocate this Victaulic

® 

VicFlex

 product properly could 

affect its performance during a fire, resulting in serious personal 
injury and property damage.

* Reference UL 2443: Section 25.1

CONNECTION TO THE SPRINKLER PIPING 

USING AN ADAPTER NIPPLE AND A 

STYLE AQC-U SPRINKLER FITTING

 WARNING

•  The flexible hose shall not be bent or fluctuated up-and-down or 

side-to-side when it is pressurized for test.

Failure to follow this instruction could cause improper sprinkler 
operation, serious personal injury, and/or property damage.

1.

  Apply pipe joint compound or PTFE thread sealant tape to the 

tapered threads of the adapter nipple, in accordance with the pipe 
joint compound or tape manufacturer’s instructions. Using a pipe 
wrench, tighten the adapter nipple into the sprinkler piping.

2.

  Confirm that the seal inside the nut of the Style AQC-U is in place 

and is free from damage prior to installation. Connect the nut to 
the adapter nipple, as shown above.

• 

DO NOT use pipe joint compound or PTFE thread sealant tape on 
the threads of the adapter nipple. The seal inside the nut of the 
Style AQC-U provides the leak-proof connection.

• 

Tighten the connection nut to a torque of 40 ft-lbs/54 N•m 
(approximately 1/2 to 3/4 of a turn past hand-tight). 

NOTE:

 To prevent 

damage to the seal, tighten the assembly by applying torque only 
to the connection nut and DO NOT exceed the specified torque.