background image

I-V9

INSTALLATION INSTRUCTIONS

Style V9 Victaulic

®

 FireLock

 IGS

  

Installation-Ready

 Sprinkler Coupling

I-V9_1

REV_B

IMPORTANT INFORMATION

INCORRECT - Orignal Groove System (OGS) Groove Profile

CORRECT - IGS Groove Profile

The Style V9 Victaulic

®

 FireLock

 IGS

 Installation-Ready

 Sprinkler 

Coupling shall be used 

ONLY

 with sprinkler piping connections that are 

prepared to Victaulic IGS proprietary groove specifications. 

DO NOT

 

attempt to install the Style V9 on sprinkler piping connections that are 
prepared to any other groove specification. Refer to Victaulic publication 
25.14 for the IGS groove specification, which can be downloaded at 
victaulic.com.

INSTRUCTIONS FOR THE INITIAL 

INSTALLATION OF A STYLE V9

DO NOT REMOVE 

NUT/BOLT FOR INITIAL 

INSTALLATION

1. DO NOT DISASSEMBLE THE STYLE V9:

 The Style V9 is designed 

so that the installer does not need to remove the bolt and nut for 
installation. This facilitates installation by allowing the installer to directly 
install the Style V9 onto the sprinkler piping’s grooved end.

2. CHECK GROOVED END OF 
SPRINKLER PIPING:

 The outside 

surface of the sprinkler piping, 
between the groove and the end 
of the sprinkler piping, shall be 
generally free from indentations, 
projections, weld seam anomalies, 
and roll marks to ensure a leak-
tight seal. All oil, grease, loose 
paint, dirt, and cutting particles 
shall be removed.

The sprinkler piping’s outside diameter (“OD”), groove dimensions, 
and maximum allowable flare diameter shall be within the tolerances 
published in current Victaulic IGS specifications, publication 25.14, 
which can be downloaded at victaulic.com.

Gasket Grade 

Color Code Mark

3. 

Check the gasket to verify 

that it is suitable for the intended 
service. The color code identifies 
the material grade. Refer to 
Victaulic publication 05.01 for 
the color code chart, which can 
be downloaded at victaulic.com. 

Refer to the "NOTICE" on the 
following page for important 
gasket information.

3a. 

If any conditions listed in the "NOTICE" are met, apply a thin coat of 

a compatible lubricant, such as Victaulic Lubricant or silicone lubricant, 
only to the gasket sealing lips.

 CAUTION

•  If any conditions listed in the "NOTICE" are met, a thin coat of a 

compatible lubricant shall be applied only to the gasket sealing 
lips to prevent pinching, rolling, or tearing during installation.

Failure to use a compatible lubricant may cause gasket damage, 
resulting in joint leakage and property damage.

 

WARNING

•  Read and understand all instructions before attempting to install any Victaulic products.
•  Always verify that the piping system has been completely depressurized and drained immediately 

prior to installation, removal, adjustment, or maintenance of any Victaulic products.

•  Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious  personal injury and property 
damage.

  

•  The Style V9 Victaulic

®

 FireLock

 IGS

 Installation-Ready

 Sprinkler Coupling shall be used only in fire protection systems that are 

designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or 
equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information 
regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc.

•  The Style V9 shall be used only for sprinkler-piping-to-sprinker connections. DO NOT use the Style V9 for pipe-to-pipe connections.
•  These installation instructions are intended for an experienced, trained installer. The installer shall understand the use of this product and 

why it was specified for the particular application.

•  The installer shall understand common industry safety standards and potential consequences of improper product installation.
Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system 
failure, resulting in death or serious personal injury and property damage.

Содержание V9 FireLock IGS

Страница 1: ...ortant gasket information 3a If any conditions listed in the NOTICE are met apply a thin coat of a compatible lubricant such as Victaulic Lubricant or silicone lubricant only to the gasket sealing lips CAUTION If any conditions listed in the NOTICE are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to prevent pinching rolling or tearing during installati...

Страница 2: ...tempting to install and tighten the Style V9 onto the sprinkler piping s grooved end Failure to follow these instructions could result in serious personal injury and property damage 4 ASSEMBLE JOINT Assemble the joint by installing the Style V9 onto the sprinkler piping s grooved end until contact with the center leg of the gasket occurs Rotate the sprinkler and Style V9 so that the frame arms and...

Страница 3: ...assembly Perform trial assemblies with the impact wrench and check the assemblies with a torque wrench to help determine the suitability of the impact wrench Using the same method periodically check assemblies throughout the system installation For safe and proper use of impact wrenches always refer to the impact wrench manufacturer s operating instructions In addition verify that proper impact gr...

Страница 4: ...d Feature of Bolt Pad 7 INSTALL BOLT Install the bolt through the housings Verify that the head of the bolt faces the angled feature of the bolt pad as shown above 8 INSTALL NUT Thread the bolt into the nut until the top of the nut is flush with the end of the bolt as shown above Verify that the gasket remains seated in the gasket pocket of the housings and that the nut is engaged with the flat fe...

Отзывы: