Series 726 Vic-Ball
®
Valve
• Instructions for Lever Handle to Gear Operator Conversions
• Instructions for Adjusting Closed and Open
Travel Limit Stops on Gear Operators
Installation Instructions
• Read and understand all instructions before attempt-
ing to install, remove, or adjust any Victaulic piping
products.
• Wear hardhat, safety glasses, and foot protection.
Failure to follow these instructions could result in
serious personal injury and/or property damage.
REQUIRED PARTS
The following parts are required for installing a gear operator onto a Series 726 Vic-Ball Valve.
Qty.
Description
1
Gear Operator
1
Drive Hub
1
Stem Adapter
1
Bracket
Qty.
Description
Valve Size – inches/
millimeters
1
¹⁄₂
(40)
2
(50)
2
¹⁄₂
(65)
3
(80)
4
(100)
6
(150)
Size of Hardware (Metric)
1
Flat Washer
M6
M6
M8
M8
M10
M10
3
Lock Washer‡
M6
M6
M8
M8
M10
M10
4
Lock Washer§
M8
M8
M8
M8
M8
M8
4
Hex-Head Screw (for mounting
bracket to valve)
M6
✕
1.0
M6
✕
1.0
M8
✕
1.25
M8
✕
1.25
M10
✕
1.5
M10
✕
1.5
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
4
Hex-Head Screw (for mounting gear
operator to bracket)
M8
✕
1.25
M8
✕
1.25
M8
✕
1.25
M8
✕
1.25
M8
✕
1.25
M8
✕
1.25
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
(16 mm Long)
‡ Lock washers required for installing the bracket to the mounting plate of the valve.
§ Lock washers required for installing the gear operator to the bracket.
• Disable the system’s pump before performing any operator conversions.
• There must be ZERO differential pressure between the valve and the inlet and outlet.
Failure to follow these instructions could result in serious personal injury and/or
property damage.