![Vicruns VD530 Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/vicruns/vd530-series/vd530-series_user-manual_1013438012.webp)
Product Information VD530 Series Inverter User Manual
- 8 -
2.4 Product Specifications
Table 2-2 Product technical specification
Item
Specifications
Power input
Rated input
voltage
Grade of rated voltage is 220V or 380V: voltage continued
fluctuation±10%, brief fluctuation:-15~+10%, voltage
imbalance rated<3%, aberration rate meet IEC61800-2
requirements.
Rated input
current
Refer to table 2-1
Rated frequency
50/60Hz, fluctuation range ±5%
Power output
Standard adaptive
motor
Refer to table 2-1
Rated capacity
Refer to table 2-1
Rated current
Refer to table 2-1
Output voltage
Output three-phase under the rated input condition,
0V~rated input voltage, error is less than±3%.
Main Control
Functions
Highest frequency
50.00Hz~600.00Hz
Carrier frequency
0.5kHz~16.0kHz, auto-adjust carrier frequency.
Input frequency
resolution
0.01Hz (digit setup mode)
Control mode
Open vector, closed vector, V/F control
Start torque
0.25Hz/150% (vector)
Motor type
Asynchronous motor
Speed range
1: 100
Speed control
accuracy
±0.2%
Torque control
accuracy
5%
Overload capacity
G type motor: 150% rated current for 60sec; 200% rated
current for 1sec.
P type motor: 120% rated current for 60sec; 150% rated
current for 5sec.
Torque boost
Auto torque boost, manual torque boost by 0.1%~10.0%.
Acceleration /
deceleration curve
Linear or S curve acceleration/deceleration mode, 4 types
of acceleration/deceleration time, range 0.0s~6500.0s.
DC braking
DC braking frequency: 0.00Hz~max output frequency,
braking time: 0.0s~100.0s, braking current: 0.0%~100.0%.
Jogging control
Jogging frequency range: 0.00Hz~max output frequency,
jog acceleration/deceleration time 0.0s~6500.0s.
Содержание VD530 Series
Страница 2: ......
Страница 9: ...VD530 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...
Страница 230: ......