30 |
028-0323-02_LIT-VZ7656R&VZ7656H_W-E01_EN
September 2019
S
PECIFICATIONS
Terminal Equipment Controller power
requirements:
Operating conditions:
Storage conditions:
Sensor:
Resolution:
Temperature control accuracy:
Contact output rating
Occ, Stand-By and Unocc cooling setpoint range:
Occ, Stand-By and Unocc heating setpoint range:
Room and outdoor air temperature display range:
Digital inputs:
By-pass damper/VFD analog output rating
By-pass damper /VFD analog output accuracy:
Wire gauge:
Approximate shipping weight:
Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
19-30 VAC 50 or 60 Hz; 2 VA Class 2
RC to RH jumper 2.0 Amps 48VA max.
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Local 10 K NTC thermistor
± 0.1 °C ( ± 0.2 °F )
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F )
typical calibrated
Relay output: 30 VAC, 1 Amp.
Maximum, 3 Amp. In-rush.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F )
Dry contact across terminal DI1
0 to 10 VDC into 2K
Ω
resistance min
± 3% typical
18 gauge maximum, 22 gauge
0.75 lb ( 0.34 kg )
UL:
UL 873 (US) and CSA C22.2 No.
24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada:
ICES-003 (Canada)
FCC:
Compliant to CFR 47, Part 15,
Subpart B, Class A (US)
CE :
EMC Directive 2004/108/EC
(Europe Union)
C-Tick:
AS/NZS CISPR 22 Compliant
(Australia / New Zealand) Supplier
Code Number N10696
FCC:
Compliant to: Part 15, Subpart B,
Class (US)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION
Please check with your local government for instruction on disposal of this product