This Quick Start Guide is intended for experienced installing 
technicians. It is a basic reference to ensure all connections are 
properly made. It is for models VAX-PCR-35L and VAX-PCR-640L. 
For additional information please refer to Vicon's website 
vicon-security.com.

1.0 Introduction

A key component of a physical security electronic access control 
system, a mobile-ready reader combining BLE and proximity 
technologies is based on RFID technology. In operation  
it is capable of reading data stored on a proximity credential via radio 
frequency—or reading data from mobile credential stored in a 
smartphone’s wallet app via BLE technology—and without physical 
contact, and then passing the data obtained to the physical access 
control system. Access control systems typically manage  
and record the movement of individuals through a protected area, 
such as a locked door.

2.0 Mounting Provisions

Each reader may be installed either indoors or outdoors. Mounting 
options shown in the table below. Use supplied #6 mounting screws, 
or equivalent security screws, for installation.

 

Model

Mullion Mount

Single-Gang Wall Mount*

VAX-PCR-35L

VAX-PCR-640L

*Plastic or metal.

3.0 Reader Wiring

Wiegand

Magstripe

Conductor

Function

Conductor

Function

Red

DC (8-14 VDC)

Red

DC (8-14 VDC)

Black

Ground

Black

Ground

Green

Data 0

Green

Clock

White

Data 1

White

Data

Brown

Red LED

 a

Brown

Red LED

Orange

Green LED

 b

Orange

Green LED

Yellow

Not Used

Yellow

Not Used

Blue

Beeper

Blue

Beeper

Violet

Not Used

Violet

Not Used

Drain

Shield Ground

Drain

Shield Ground

4.0 Cable Requirements

24 AWG minimum, multi-conductor stranded with an overall foil shield, 

for example Belden 9535 or similar, supporting the five conductors 

comprising the physical layer of the Wiegand interface (power, 
ground, data 0, data 1, and/or beeper and LED). Alternatively, Belden 
9539 or similar, for all reader functions. Contact your access control 

system manufacturer for their specific requirements. Per the SIA’s 
Wiegand specification, maximum cable length is 500 feet (152 m).

5.0 Output Formats

•  Wiegand (industry standard 26-bit Wiegand and custom
   Wiegand formats)
•  Magnetic Stripe (ABA Track II, clock and data, with card present)

6.0 Grounding

Shield (drain) continuity must run from the reader to the access  
panel. Shield (drain) and reader ground must be tied together at  
the access panel and connect to an earth ground at one point.

7.0 Power

Reader may be powered by the access panel. A linear power  
supply is recommended for best operation.

8.0 Voltage and Current

Voltage: 8 to 14 VDC
Current Draw: 60mA typical, 90mA peak

9.0 Connection

Connection must be done in accordance with NFPA 70. Do  
not connect to a receptacle controlled by a switch. Connect  
to a power limited DC voltage source.

10.0 Troubleshooting

1.  When the reader is first powered on it will beep 4-times, 

 

and the LED will shine red.

2.  Presenting a supported access credential will result in the  

reader beeping and the LED flashing once.

3.  Mobile operation is optimized for smartphones supporting  

BLE (Bluetooth LE) version 4.2 or newer. Further, for  
the downloading of mobile access credentials, a stable,  
high-quality internet connection is recommended.

NOTE: The access panel controls LED functionality, such as  
switching the LED to green.

XX274-85

WIRING NOTES:

a

Single Line LED:

 This is the standard operating mode and does not make  

use of the Orange conductor. The LED is Red when the reader is idle and  

flashes when a card is presented. The LED turns Green when the Brown 

Conductor is pulled low by the access control panel.

b

Dual Line LED: 

This mode makes use of both the Brown and Orange 

conductors. The Brown conductor controls the Red LED and the Orange 
conductor controls the Green LED. LED states are determined by the 
access control system option and capability.

Unused conductors should be trimmed, isolated and taped back to prevent 

unintended current flows. Apply positive voltage only to the Red DC Conductor.

QUICK INSTALLATION GUIDE

VAX-PCR-35L AND VAX-PCR-640L 

 

MOBILE-READY PROXIMITY READERS