/MTS-5800 Network Tester

  

TCP Throughput Testing to an iPerf v3 Server 

 

This document provides instructions on how to configure and execute TCP Wirespeed Throughput test 
from a T-BERD/MTS 5800 instrument to an iPerf v3 server. 
 

Equipment Requirements: 

 

T-BERD/MTS-5800 equipped with the 
following: 

o

 

BERT software release V28.1 or greater 

o

 

Ethernet and Layer4 test options: 

 

C510M1GE and C5LSLAYER4 for  
10/100 Megabit or 1 Gigabit Ethernet 

 

C510GELAN and C510GLAYER4 for  
10 Gigabit Ethernet 

o

 

SFP or SFP+ optical transceiver to match the 
line under test 

 

Patch Cables to match the optical 
transceiver and line under test (CAT5E, 
Single mode or Multimode Fiber) 

 

Fiber optic inspection microscope (VIAVI 
P5000i or FiberChek Probe) 

 

Fiber Optic Cleaning supplies 

 

 

Figure 1: Equipment Requirements

 

The following information is required to complete the test:

 

 

 

Physical Interface (10/100/1000BASE-T, 1000BASE-SX, 1000BASE-LX, 10GBASE-LR, etc.) 

 

Auto Negotiation settings of the port under test. 
 

Fiber Inspection Guidelines: 

 

All fiber end-faces must be clean and pass 
an inspection test prior to connection. 

 

Use the VIAVI P5000i, FiberChek Probe, or 
Sidewinder microscope to inspect both 
sides of every connection being used 
(SFP/QSFP Port, bulkhead connectors, 
patch cables, etc.) 

 

Figure 2: Inspect Before You Connect 

Содержание T-BERD/MTS-5800

Страница 1: ...match the line under test Patch Cables to match the optical transceiver and line under test CAT5E Single mode or Multimode Fiber Fiber optic inspection microscope VIAVI P5000i or FiberChek Probe Fiber Optic Cleaning supplies Figure 1 Equipment Requirements The following information is required to complete the test Physical Interface 10 100 1000BASE T 1000BASE SX 1000BASE LX 10GBASE LR etc Auto Neg...

Страница 2: ...le with the interface under test Launch and Configure Test 1 Press the Power button to turn on the test set and view the startup screen 2 Using the Select Test menu Quick Launch menu or Job Manager launch an Ethernet Layer 4 TCP Wirespeed IPv4 Terminate test on port 1 for the desire physical interface For example Ethernet 10 100 1000 Layer 4 TCP WIrespeed IPv4 P1 Terminate 3 If the test is not in ...

Страница 3: ... 5800 to iPerf server direction or to Downstream to test in the iPerf server to TBERD 5800 direction 12 Set the Connect to Server parameter to the IP address of the iPerf server 13 Set the Connect to Port parameter to TCP port the iPerf server is listening on 14 Set the Window Size parameter to 4194304 bytes 15 If required adjust the Max Seg Size parameter to match the circuit under test configura...

Страница 4: ...w and be relabeled 3 Ensure the TBERD 5800 test port established a link to circuit under test as indicated by green Signal Present optical test port only Sync Acquired and Link Active LEDs 4 Set the real time test results view to TCP Host Detailed L4 Stats 5 To start the TCP Throughput test tap on the Start TCP Client button on the Actions tab at the bottom of the screen and observe the real time ...

Отзывы: