Chapter 3: Setting Reference
It is necessary perform a set reference measurement when reference cords or
adapters are removed and re-attached. If there is a mismatch in firmware versions,
Certifier will deny Autotest. Please also check that calibration is not expired before
testing.
1. Connect the unpinned end of the tail cords to the Local and Remote units.
2. Connect each pinned end of the tail cord to a connector.
3. Connect a Type A or Type B reference cord to the other end of the
connectors.
4. Press the TOOLS button > Set Reference to begin set reference.
Reference cord type should be the same as the MPO cable to be tested.
unpinne
d
pinned
unpinne
d
pinned
Type A or B reference cord
Test cord
Test cord