090427.02
13
vetus®
Waste water control panel WWCP
ENGLISH
2
Operating instructions
Function of the LEDs
Off:
the panel is switched off.
Green:
the panel is switched on.
Green
flashing:
the battery voltage is less than 8 Volts.
Off:
-
Green:
the pump cycle is set to manual operation
Off:
the auto mode is not switched on.
Green:
the auto mode is switched on.
Electrically operated
shut-off valve with status
feedback
Manually operated shut-
off valve without status
feedback
Off:
-
Green:
the shut-off valve is
closed.
-
Green
flashing:
the shut-off valve is either
opening or closing.
the pump cycle is active.
the shut-off valve is
opened.
Red:
opening or closing has
not been successful
within 40 seconds.
-
Green:
the pump is switched on.
Red:
the pump is switched on but the level in the tank has
not dropped by 10% within the set time.
The LEDs have different functions during set up; see 4 Set-up procedure.
Switching on or off
The panel is switched on or off by using the key
. The level in the waste water tank is indicated
after switching on. Levels 25%, 50% and 75% are shown with a green LED. The red 100% LED will
come on at 90%. The red 100% LED will flash when the level is higher than 95%.