Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
37 of 146
Troubleshooting
This section describes how to troubleshoot using the Front-Panel Menu of the Elite-RS Panel.
Perform troubleshooting techniques on the Elite-RS Panel when messages on the front-panel are not consistent with
those described in “Confirming a Successful Installation”.
Options on the Front-Panel Menu include:
Test Zones
The TEST ZONES menu tests NAC, panel and loop outputs. Options for this menu feature are described below:
Refer to Section 4, “Front-Panel Menu” for more information about Test Zones.
Test Zones reverts to the MAIN MENU after 25 seconds when there is no navigation activity on the
front-panel display.
To troubleshoot using the TEST ZONES menu feature:
7
Re-connect the black-lead to the negative terminal of the standby-battery in the Elite-RS Panel.
The LCD display provides the following message to identify the return to the normal-standby condition:
Test Zones
Tests zones 1 to 500 including local NACs, panel outputs and loop outputs.
Event Log
Provides event log view function as well as an event log clear function.
Loop Data Test
Tests devices connected to Elite-RS Panel loops.
Test Zones
Default = 1
Sets the test for zones 1 to 500.
Local NACs
Default = On
Tests Elite-RS Panel NACs. Audible and visual notification
circuits activate for 3-second durations during this test.
Loop Outputs
Default = Off
Tests loop driven outputs other than the loop sounders.
1
Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.
SET ACCESS LEVEL 2 MENU
Enter Access Level 2 Password
Use numbered arrow keys
*****
Access will automatically expire after
120 seconds if no key is pressed.
ENTER TO PROCECEED – EXIT TO QUIT
2
Type the five digit code in the password field and press Enter.
The default password is 22222.
11:08 Tuesday 04 August 2009
AUTO CONFIGURED PANEL
USE ARROW KEYS TO ENABLE PANEL
PRESS ? FOR HELP