Testing the Panel Lamps
Trouble-Silence Test
This test checks the silencing operation of the Elite-RS Panel during a trouble condition.
To perform the Trouble-Silence Test:
1
Press the lamp test button to light the front-panel lamps.
2
Verify that all front-panel lamps are lit.
Contact the help desk if front-panel lamps do not light.
Reference Section 2, “Overview” for a description of Lamp Test operation.
1
Confirm that the Elite-RS Panel is in the Normal-Standby mode before performing this test.
The Normal-Standby mode is shown below:
The first line of the message format contains the time, day and date.
The second line of the format contains a default or user defined message.
2
Press any numeric arrow-button on the right-control-panel or turn the enable key-switch to the right to display
“SET ACCESS LEVEL 2 MENU” on the LCD.
3
Provide Access Level 2 authorization and then press Enter on the right-control-panel.
Fire
AC Power On
Pre-Alarm
On Test
More Events
Point
Bypassed
General Trouble
Power Trouble
Supervisory
NAC Trouble
Panel
Sounder
Silenced
Delay Active
Programmable
Function
Enable Access
Alarm
Silence
Panel Sounder
Silence
Lamp
Test
Reset
Fire Drill
Re-Sound
Alarm
1
2
3
4
?
More
Events
More
Fire Events
Enter
Exit
11:08 Tuesday 04 August 2009
AUTO CONFIGURED PANEL
USE ARROW KEYS TO ENABLE PANEL
PRESS ? FOR HELP
11:08 Tuesday 04 August 2009
AUTO CONFIGURED PANEL
USE ARROW KEYS TO ENABLE PANEL
PRESS ? FOR HELP