Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
31 of 146
Connecting Auxiliary 24 VDC
The 24 V OUT and AUX 24 V power-source can be used to operate expansion-boards or low-current
auxiliary-devices. Devices connected to these terminals must not draw current in excess of 360 mA on each of these
outputs. Connect circuits to terminals 11 and 12 for the 24 V OUT power-source. Connect circuits to terminals 13 and
14 for the AUX 24 V power-source.
Provide cabling connections to these outputs using wire with a 3 volt maximum line loss.
Maintain these connections using the wire gages defined in Appendix A, Specifications.
Reference Appendix B, “Equipment List” for the list of devices authorized for these outputs.
Relay Contacts
Configurable dry Form C relays are located on the Elite-RS Panel for providing contact-actuation. The relays can be
operated from default parameters or configured for specific functions in Loop Explorer or eSP Discovery.
Relay contacts of the Elite-RS Panel include:
The figure below illustrates an example circuit using the normally-open contacts of the trouble relay:
Figure 3-22
Trouble Relay Example
The adjacent figure illustrates a trouble-condition caused by the absence of end-of-line resistors and end-of-line-
devices on terminals of the Elite-RS Panel.
Trouble
The default operation of this relay is set to perform a Trouble output. Configurable settings are
provided for Delay, Alarm Silence, Zone and Location Text. Default settings for these attributes
are disabled from operating.
Fire
The default operation of this relay is set to perform a General Alarm and Emergency output.
Configurable settings are provided for Delay, Alarm Silence, Zone and Location Text.
Default settings for these attributes are disabled from operating.
Supervisory
The default operation of this relay is set to perform a Supervisory Alarm output and the
Alarm Silence button is enabled for operating. Configurable settings are provided for Delay,
Zone and Location Text. Default settings for these attributes are disabled from operating.
24V OUT AUX 24V
+ -
+ -
NC C NO
TROUBLE
NC C NO
FIRE
NC C NO
SUPERVISORY
NAC 1
NAC2
+ -
+ -
SLC1 OUT SLC1 IN
+ -
+ -
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
TROUBLE LAMP