8.4 Vertiv™ VRC-S with VRC split lee temp 208V NAM
VRC-S SKUs
VRCS3350-208VSL
VRCS3300-208VSL
VRCS3307-208VSL
VRCS3357-208VSL
Configured system
weight
270 kg (595 lb.)
225 kg (496 lb.)
261 kg (575 lb.)
288 kg (635 lb.)
Shipping weight
336 kg (741 lb.)
278 kg (613 lb.)
314 kg (692 lb.)
354 kg (781 lb.)
Sound (At 60% fan
speed and 40%
compressor speed)
52.5 dBA @ 1 m
52.5 dBA @ 1 m
52.5 dBA @ 1 m
52.5 dBA @ 1 m
Rack dimensions U; H,
W, D
42U; 2000 mm, 800 mm,
1200 mm (78.6 in., 31.5 in.,
47.8 in.)
42U; 2000 mm, 600 mm,
1200 mm (78.6 in., 23.6 in.,
47.8 in.)
48U; 2200 mm, 600 mm,
1200 mm (86.6 in., 23.6 in.,
47.8 in.)
48U; 2200 mm, 800 mm,
1200 mm (86.6 in., 31.5 in.,
47.8 in.)
Usable space available
for IT equipment
36U
36U
42U
42U
Shipping weight of rack
N / A
N / A
N / A
N / A
Shipping dimensions of
rack H, W, D
2134 mm, 826 mm, 1385 mm
(84 in., 32.5 in., 54.5 in.)
2134 mm, 626 mm, 1385 mm
(84 in., 24.6 in., 54.5 in.)
2396 mm, 626 mm, 1385 mm
(94.3 in., 24.6 in. 54.5 in.)
2396 mm, 826 mm, 1385 mm
(94.3 in., 32.5 in., 54.5 in.)
rPDU (Pre-installed in
rack)
VP8641
VP5870V
rPDU sub-type
Switched
Switched
rPDU type
Outlet Level Monitoring
Outlet Level Monitoring
Voltage
208 V
208 V
Input current
30 A
30 A
Regularoty derated
input current (North
America)
24 A
24 A
rPDU rated maximum
4.9 kW
4.9 kW
Horizontal/Vertical
Vertical
Vertical
rPDU input plug
NEMA L6-30P
NEMA L6-30P
Cord length
3 m
3 m
Outlets
(20) U-Lock IEC C13 (4) U-Lock IEC C19
NOTE: (2) U-Lock IEC C13 outlets will be required
and preprogrammed for the backup fan and
condensate pump
(30) U-Lock IEC C13 (6) U-Lock IEC C19
NOTE: (2) U-Lock IEC C13 outlets will be required
and preprogrammed for the backup fan and
condensate pump
Vertive Intelligence
Director enabled
YES
YES
Geist Upgradable 2.0
protocols supported
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP,
DNS, HTTP, HTTPS (TLSv1.2), SMTP, SMTPS, DHCP, SNMP
(v1/v2c/v3), LDAP, NTP, SSH, and Syslog
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP,
DNS, HTTP, HTTPS (TLSv1.2), SMTP, SMTPS, DHCP, SNMP
(v1/v2c/v3), LDAP, NTP, SSH, and Syslog
Certifications/Agency
approvals
UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class A
Conformance
UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class
A Conformance
Cooling Kit Type
VRC201KIT
Cooling capacity
0.9 kw-3.5 kW
8 Specifications
46
Vertiv™ VRC-S User Manual
Содержание VRC-S
Страница 1: ...VRC S User Manual...
Страница 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...
Страница 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...
Страница 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...
Страница 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...
Страница 65: ...Vertiv VRC S User Manual...