BUNDLE
FROM
TO
FACTORY/FIELD-SUPPLIED
WIRING
PRIMARY PDX/PCW & CONTROL PANEL (All Configurations)
1
Fire Control Panel
Smoke Detector
FACTORY
2
TB1(P1- 3pin connector, Positions 7, 8, and GND)
PDX Top Plenum (P1- 3pin
connector)
FACTORY
3
TB2 (P2 - 4pin connector, Positions 3, 4, 23, and 24)
PDX / PCW (P2 - 4pin connector,
Positions 75, 76, 37, and 38)
FACTORY
4
TB2 (P3 - 3pin connector, Positions 5 and 6)
PDX Top Plenum Thermostat (P3 -
3pin connector, Positions 5 and 6)
FACTORY
5
Supply Air Temp Sensor
PDX/PCW iCOM board
FACTORY
6
2T Sensor
Adjacent 2T Sensor
FACTORY
7
Rack Temp Sensor to PDX / PCW Sensor
PDX /PCW Return Air Sensor
FACTORY
8
Emergency Fan
Adjacent Emergency Fan
FACTORY
9
Load-center AC Power Input
Load center
FIELD
10
PDX AC Power Input
PDX
FIELD
11
MC Condenser AC Power Input
MC Condenser
FIELD
12
PDX / MC Piping
MC Condenser
FIELD
13
PDX Condensate Piping
Drain
FIELD
14
Fire Control Panel
Building Fire System
FIELD
15
PDU Power Input
Load center
FIELD
16
EPO
UPS or UTILITY FEED
FIELD
SECONDARY PDX/PCW (Redundant / Higher Capacity Configurations) & OPTIONAL LOAD CENTER
1
Secondary PDX / PCW (P2R - 4pin connector)
TB2 (P2R - 4pin connector)
FACTORY
2
Secondary Top Plenum - Thermostat (P3R - 3pin connector)
TB2 (P3R - 3pin connector)
FACTORY
3
Supply Air Temp Sensor
PDX/PCW iCOM board
FACTORY
4
Secondary [[[Undefined variable ctrl_panel_fire_
suppress.PComponent4]]] Smoke Detector to Primary Smoke
Detector
Smoke Detector
FACTORY
5
Rack Temp Sensor to PDX / PCW Sensor
PDX /PCW Return Air Sensor
FACTORY
6
Optional Secondary Load-center AC Power Input
Load center
FIELD
7
Secondary PDX AC Power Input
PDX
FIELD
8
Secondary MC Condenser AC Power Input
MC Condenser
FIELD
9
Secondary PDX / MC Piping
MC Condenser
FIELD
10
Secondary PDX Condensate Piping
Drain
FIELD
11
vNSA AC Power
Load center
FIELD
12
vNSA Network
PDX
FIELD
Table 11.4 DCR field-wiring list
Vertiv
| SmartRow DCR Installer/User Guide |
80
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......