Vertiv™ NetSure™ DC/DC Converter Module User Manual 

 

Important Safety Instructions 

Safety Admonishments Definitions 

Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv. 

General Safety 

 

DANGER!  

YOU MUST FOLLOW APPROVED SAFETY PROCEDURES. 

Performing the following procedures may expose you to hazards.  These procedures should be performed by qualified 
technicians familiar with the hazards associated with this type of equipment.  These hazards may include shock, energy, 
and/or burns.  To avoid these hazards: 

a)

 

The tasks should be performed in the order indicated. 

b)

 

Remove watches, rings, and other metal objects. 

c)

 

Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the expected 
voltage is present.  Check for voltage with both AC and DC voltmeters prior to making contact. 

d)

 

Wear eye protection. 

e)

 

Use certified and well maintained insulated tools.  Use double insulated tools appropriately rated for the work to be 
performed. 

Voltages 

DC Input Voltages 

 

DANGER!  

This system operates from DC input voltage.  Although the DC voltage is not hazardously high, the input power 

can deliver large amounts of current. 

DC Output and Battery Voltages 

 

DANGER!  

This system produces DC power and may have a battery source connected to it.  Although the DC voltage is not 

hazardously high, the converters and/or battery can deliver large amounts of current.  Exercise extreme caution not to 
inadvertently contact or have any tool inadvertently contact an output terminal or battery terminal or exposed wire 
connected to an output terminal or battery terminal.  NEVER allow a metal object, such as a tool, to contact more than one 
termination or battery terminal at a time, or to simultaneously contact a termination or battery terminal and a grounded 
object.  Even a momentary short circuit can cause sparking, explosion, and injury. 

Personal Protective Equipment (PPE) 

 

DANGER!  

ARC FLASH AND SHOCK HAZARD. 

Appropriate PPE and tools required when working on this equipment.  An appropriate flash protection boundary analysis 
should be done to determine the “hazard/risk” category, and to select proper PPE. 

 

Only authorized and properly trained personnel should be allowed to install, inspect, operate, or maintain the equipment. 

 

Do not work on LIVE parts.  If required to work or operate live parts, obtain appropriate Energized Work Permits as required 
by the local authority, per NFPA 70E “Standard for Electrical Safety in the Workplace”. 

Содержание Netsure

Страница 1: ...NetSure DC DC Converter Module User Manual Specification Number 1C48582000P3 Model Number C48 58 2000P3...

Страница 2: ...specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains confidential and pro...

Страница 3: ...s 5 1 2 4 Compliance Information 5 1 2 5 Standard Features 6 1 2 6 Mechanical Specifications 7 2 Operation 7 2 1 Local Indicators 7 2 2 Converter High Voltage Shutdown and Lockout Restart 8 2 3 Conver...

Страница 4: ...SI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts the...

Страница 5: ...rdously high the input power can deliver large amounts of current DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC volt...

Страница 6: ...static sensitive components discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm resistor Some wrist straps have a built in one megohm resistor no exte...

Страница 7: ...verage 2000W peak The C48 58 2000P3 can provide 2000 watts peak and 1600 watts average This is based on a cyclic load profile of 2000 watts for 7msec and 600 watts for 3msec Output Characteristics Ref...

Страница 8: ...48 VDC and temperature range is from 10 C to 55 C c Dynamic Response The dynamic response time at rated input and output voltage is 200us and overshot 5 for load changes at 50 25 50 and 50 75 50 d Th...

Страница 9: ...GR 947 CORE 38 dBrnC between 5 100 of the maximum load output voltage 56 VDC Ripple Attenuation Ripple attenuation is better than 24dB input to output and f 360Hz 1 2 2 DC Input Ratings Voltage Nomina...

Страница 10: ...4 91 166 75 70 28 90 94 49 210 29 80 33 19 94 02 260 81 90 37 55 93 48 319 92 100 41 90 94 96 280 34 53 5 VDC 10 3 30 90 79 50 36 20 6 35 94 38 61 48 30 9 43 95 31 76 89 40 12 57 95 32 102 32 50 15 73...

Страница 11: ...as the office environment 1 2 4 Compliance Information Safety Compliance This unit meets the requirements of UL 62368 1 Standard for Information Technology Equipment and is UL Recognized as a power s...

Страница 12: ...y The converter can be inserted or removed from a live DC power system with no damage When the converter is plugged into the system the sub system output voltage will not be affected Cooling Each conv...

Страница 13: ...put Voltage Protection High Temperature Protection Thermal Derating Address Code Date Software Version Hardware Version Imbalance Output Current 1 2 6 Mechanical Specifications Weight 1 13kg 2 49 lbs...

Страница 14: ...onverter The converter may also be restarted from the controller Refer to the controller s documentation 2 3 Converter Current Limit When setting total converter current limit the set point to each co...

Страница 15: ...energized might represent a hazard during servicing after operation of the fuse WARNING To prevent damage to the latching mechanism ensure the handle is in the open position when installing or removin...

Страница 16: ...r is properly seated in the shelf If the current sharing imbalance still persists following the verification suggested above replace the converter exhibiting the current imbalance 3 1 2 Converter Modu...

Страница 17: ...ve the converter wait 30 seconds or more until the LEDs on the converter extinguish then re insert the converter If converter fails to start shuts down again or load sharing imbalance persists replace...

Страница 18: ...odule completely into the shelf 7 Push the handle up into the module s front panel This will lock the module securely to the shelf Tighten the captive screw on the handle 8 Certain functions i e conve...

Страница 19: ...NetSure DC DC Converter Module User Manual Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv https www twitter com...

Страница 20: ...e trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility...

Отзывы: