Vertiv NetSure V200D50 Скачать руководство пользователя страница 16

 
 

Vertiv

 

|

 

NetSure V200D50 DC Power Retrofit Installation & User Manual (UM486527803)

 

|

 

Rev. F 

16 

 

The fan is turned off when input voltage is abnormal such as very low or high input voltage. 

 

The fan starts at half speed when the rectifier starts up. 

 

A fan failure is detected and reported to the Controller.  In addition, the fault indicator (red) on the 
Rectifier front panel will flash and the Rectifier will also inhibit its output. 

 

Full fan speed is customer selectable via the Controller. 

Active Load Sharing (Rectifier):  Each Rectifier uses advanced digital active load sharing technology that 
maintains balancing to within ±1.5A.  The difference in the average current between Rectifiers is <±1.5A for loads 
in the 10 to 100% range. 

Load Sharing (via system MCA):  The MCA load sharing feature automatically balances the load.  If the MCA's 
load sharing feature is disabled for any reason, pre-programmed slope control in each PCU or Retrofit balances 
the load.  The MCA's load sharing feature is disabled whenever the system is in current limit, the system is 
delivering more than 97% capacity, or the system is delivering less than 3% capacity. 

 

NOTE!  

For optimal load sharing between the V200 Retrofits and legacy V200 PCUs, MCA version 4.2.0 

or newer is required.  With earlier MCA versions, system functionality is maintained; however, load 
sharing will not be proportional. 

Communication Failure:  A rectifier’s protection indicator (yellow) will begin flashing should it experience a 
communication failure.  The failure information will be reported to the Controller and the Controller will process 
the failure accordingly.  During a communication failure, in order to protect the battery, rectifier output voltage 
will automatically adjusted to a default value of 53.5 V.  The rectifier will revert to normal operation once normal 
communication is restored. 

Imbalance of Rectifier Output Current:  When the output current of a rectifier in a DC power system is 
unbalanced, the rectifier having the unbalanced output current will be identified automatically and its 
protection indicator (yellow) will illuminate. 

The failure information will be reported to the Controller and the Controller will process the failure 
accordingly. 

Paralleling:  A Power System equipped with V200 Retrofits may be connected in parallel with any rectifier of the 
same polarity and adjusted to the same output voltage. 

Weight:   58 Lbs. (Mounting Frame with Three Rectifiers) 

 

INSTALLATION 

Safety Statement 

 

DANGER!  

INSTALLERS MUST FOLLOW APPROVED SAFETY PROCEDURES. 

Hazardous AC and DC power sources are connected to, and are present within, the Power System.  
Following this installation procedure will minimize the possibility of personal injury or equipment damage.  
Refer to the documentation provided with your Power System for any installation or maintenance 
procedures beyond the scope of this upgrade procedure. 

Содержание NetSure V200D50

Страница 1: ...NetSure V200D50 DC Power Retrofit Installation and User Manual UM486527803 Revision F Specification Number 486527803 Model Number V200D50...

Страница 2: ...ools and materials to be used in performing procedures not specifically described in this document This document may contain confidential and or proprietary information of Vertiv Group Corporation and...

Страница 3: ...Features 13 Installation 16 Safety Statement 16 Remove Style Strips from Power Bay 17 Remove the Power Conversion Unit PCU or Blank Cover Panel 17 Install the Mounting Frame 19 Install the Rectifiers...

Страница 4: ...f not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA...

Страница 5: ...ouble insulated tools appropriately rated for the work to be performed Personal Protective Equipment PPE DANGER ARC FLASH AND SHOCK HAZARD Appropriate PPE and tools required when working on this equip...

Страница 6: ...necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle...

Страница 7: ...adjustable output current continues to increase but output voltage decreases as required to maintain constant output power Rectifiers operate in the Constant Power Mode unless load continues to increa...

Страница 8: ...Based on Input Voltage See Figure 2 Figure 2 Output Power vs Input Voltage Regulation Rectifier Default a Voltage Regulation 1 b Load Regulation 0 5 c Line Regulation 0 1 d Overshoot at Startup 1 e Dy...

Страница 9: ...the range of 176 to 264 volts shall not cause the output voltage to deviate outside the 0 5 regulation band Filtering with or without battery Typical readings were taken at nominal input voltage nomin...

Страница 10: ...2607 97 66 94 68 473 50 14 320 5160 5126 99 36 95 67 757 75 21 500 7751 7731 99 74 95 57 1169 100 28 850 10403 10388 99 86 94 73 1869 110 31 280 11284 11269 99 88 94 30 2192 120 31 280 11280 11266 99...

Страница 11: ...2672 2594 5 97 10 94 50 486 50 14 34 5171 5130 99 20 95 70 752 75 21 34 7694 7669 99 70 95 60 1161 100 28 87 10412 10395 99 80 94 60 1910 110 31 298 11285 11270 99 86 94 40 2139 120 31 23 11263 11246...

Страница 12: ...r limited for heights above 2000 m Ventilation Requirements When equipped with V200 Retrofits a VPS Power Bay must be mounted so ventilating openings are not blocked and temperature of the air enterin...

Страница 13: ...ntical in systems equipped with the V200D50 Retrofits and systems equipped with the original V200D50 Power Conversion Units PCUs Refer to System Application Guide SAG582121100 for a complete descripti...

Страница 14: ...stment changes the setting of all V200 Retrofits The current limit is factory set at 100 of rated full load unless otherwise specified b Thermal Power Limiting Each rectifier continuously monitors the...

Страница 15: ...age exceeds a second non adjustable value the rectifier shuts down and locks out regardless of load Manual restart is then required The backup HVSD setpoint is 59 5V within the range of 58 5 to 60V Ou...

Страница 16: ...ill not be proportional Communication Failure A rectifier s protection indicator yellow will begin flashing should it experience a communication failure The failure information will be reported to the...

Страница 17: ...wer Bay being upgraded These conceal the mounting hardware The style strips are secured at the bottom with a captive fastener and at the top with a pin that passes through a hole in the style strip To...

Страница 18: ...ertiv NetSure V200D50 DC Power Retrofit Installation User Manual UM486527803 Rev F 18 Figure 5 Right Side View of V200 PCU Showing Location of Safety Latch and Latch Release SAFETY LATCH LATCH RELEASE...

Страница 19: ...and cause arching and pitting on the DC power connector Checking the Power Bay s Rectifier AC Data Connector in Older Style Bays Identifying Older Style Bays 1 Older style bays have Rectifier AC Data...

Страница 20: ...within 15 1 4 to 15 3 8 If a measurement is greater than 15 3 8 or less than 15 1 4 adjustment is required see next procedure Adjustment Procedure Older Style Bays Only if required 1 When adjustment o...

Страница 21: ...first for a 15 5 16 and secure the single 1 4 hex bolt first 6 With bottom secured at 15 5 16 move to the top of the AC connector and measure for 15 5 16 then secure the two Philips screws at the top...

Страница 22: ...mounting position in the Power Bay 4 Using the supplied hardware secure the Mounting Frame to the Power Bay Figure 10 Removing the Cover Panel from the Mounting Frame Electrical Connections All electr...

Страница 23: ...ey are ready for operation immediately after power is supplied to them 7 On the Power System controller MCA update the system inventory as necessary Refer to the Power System documentation for a proce...

Страница 24: ...in the Power Bay replace the left and right style strips on the front of the bay by sliding the top of the style strip up and over the pin located on top of the bay then sliding the bottom in and sec...

Страница 25: ...s to illuminate Figure 13 Status Indicators Table 1 Local Indicators Indicator Normal State Fault State Fault Cause Power Green On Off No input voltage Internal input fuse open Flashing The Rectifier...

Страница 26: ...acing a Rectifier on page 27 for procedure to remove and reinstall a Rectifier If the current sharing imbalance still persists following the verification suggested above replace the rectifier exhibiti...

Страница 27: ...ture or relocate the heat source Rectifier not inserted into the slot completely Remove and properly inset the Rectifier Protection Indicator Yellow Flashing Rectifier communication failure Check the...

Страница 28: ...into the front panel of the Rectifier This will lock the module securely to the shelf 9 After the Rectifier is physically installed in the Mounting Frame it is ready for operation immediately after p...

Страница 29: ...lacing a Rectifier for step by step instructions 4 Remove the two style strips from the front left and right edges of the VPS Power Bay being upgraded These conceal the mounting hardware The style str...

Страница 30: ...ounting Frame they are ready for operation immediately after power is supplied to them Verify that the Rectifiers are operating normally 18 On the Power System controller MCA update the system invento...

Страница 31: ...responding socket Push back the fan the side with the tag facing inward Position the rectifier front cover back into place and secure with the three previously removed screws 9 Reinstall the Rectifier...

Страница 32: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM486527803 RF 10 17...

Отзывы: