Vertiv
|
NetSure Rectifier Module User Manual (UM1R243000 / 11BJ1307WA)
|
Rev. G
16
Table 1:
Commands / signals that can be
received by the Rectifier Module
from the Controller.
Information gathered by the
Controller from the Rectifier
Module.
•
Turn On/Off
•
Voltage Walk-in On/Off
•
HVSD Reset
•
Current Limit Adjustment
•
Voltage Adjustment
•
Fan Speed Control
Enable/Disable
•
Input Voltage
•
Output Voltage
•
Output Current
•
Current Limit Setting
•
Temperature
•
Over Voltage Setting
•
On/Off Status
•
Fault Alarms, such as:
HVSD
Fan Fail
•
Protection Alarms, such as:
Input Voltage Protection
Inner DC Bus Voltage Protection
High Temperature Protection
•
Thermal Derating
•
AC Derating
•
AC Fail
•
Imbalanced Output Current
•
Address
•
Code
•
Date
•
Software Version
•
Hardware Version
OPERATION
Local Indicators
Location and Identification: Refer to
Description: There are three (3) indicators located on the rectifier’s front panel. The functions of these
indicators are as shown in
NOTE!
DC voltage must be present at the rectifier output terminals (from battery or an operating
rectifier) or AC voltage at the input terminals for local indicators to illuminate.
Rectifier High Voltage Shutdown and Lockout Restart
Procedure
1.
Turn the power to the rectifier off or remove the rectifier, wait 30 seconds or more (until the LEDs on
the rectifier extinguish), then turn the power to the rectifier on or re-insert the rectifier.