Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 63
Optional External Top-Mount Ground (Load Return) Busbar Assemblies
Features
♦
Provides a ground busbar assembly which mounts to the external top-mount battery input busbar assembly P/N 554873.
♦
Provides for installation of customer provided two-hole lugs with 3/8" clearance holes on 1" centers.
Restrictions
Requires the external top-mount battery input busbar assembly P/N 554873.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Ordering Notes
1)
Order an external top-mount ground (load return) busbar assembly per bay as required.
P/N 514688, 6000A, for use with List 1/List 101 and List 11/List 111 (no PDSC [AC Input 'Power Distribution Service
Cabinet']) or List 3/List 103, List 4/List 104, List 5/List 105, List 13/List 113, List 14/List 114, and List 15/List 115.
P/N 514689, 10000A, for use with List 1/List 101 and List 11/List 111 (no PDSC [AC Input 'Power Distribution Service
Cabinet']) or List 3/List 103, List 4/List 104, List 5/List 105, List 13/List 113, List 14/List 114, and List 15/List 115.
P/N 514690, 6000A, for use with List 2/List 102 and List 12/List 112 equipped with a List 30 or List 31 PDSC (AC Input
'Power Distribution Service Cabinet').
P/N 514691, 10000A, for use with List 2/List 102 and List 12/List 112 equipped with a List 30 or 31 PDSC (AC Input 'Power
Distribution Service Cabinet').
POSITIVE BATTERY
(GROUND RETURN)
BUSBAR
NEGATIVE BATTERY
(SUPPLY -48V)
P/N 528482
Mounted to
P/N 554873
Busbar Shield Kit (P/N 528482)
BUSBAR