List 36: Surge Suppression for 208 VAC Input PDSC
Features
♦
Provides two (2) surge suppression assemblies for the PDSC. One wired to rectifier AC input circuit breakers CB1, CB3,
CB5, CB7, and CB9. The other to CB2, CB4, CB6, CB8, and CB10.
♦
100kA interrupting capacity.
♦
Overcurrent fusing and thermal protection.
Restrictions
only.
See
in the SPECIFICATION section for additional ratings.
Please note that List 35, List 36, List 37, and List 38 Transient Voltage Surge Protector (TVSS) units designed to be used with
solidly grounded electrical systems and are not compatible with High Resistance Grounding for electrical systems. On a HRG
system, L-G voltage rises to the rated line voltage during a bolted ground fault. At this voltage the TVSS which is expecting
to see a Line to Neutral Voltage would read a Line to Line Voltage across it, which would stress the TVSS and eventually
cause the TVSS to fail.
Ordering Notes
1)
Order if additional surge suppression is required.
2)
A wire harness is factory connected to Form-C relay contacts located on each surge suppression assembly for remote
monitoring. Connect the wire harness to the controller’s binary inputs. The controller then provides alarm display
messages and an audible alarm when a surge suppression assembly activates.
List 37: Surge Suppression for 208 VAC Input
Features
♦
Provides two (2) surge suppression assemblies for the power only bay. One wired to rectifier AC input circuit breakers
CB1, CB3, CB5, CB7, and CB9. The other to CB2, CB4, CB6, CB8, and CB10.
♦
100kA interrupting capacity.
♦
Overcurrent fusing and thermal protection.
Restrictions
See
in the SPECIFICATION section for additional ratings.
Please note that List 35, List 36, List 37, and List 38 Transient Voltage Surge Protector (TVSS) units designed to be used with
solidly grounded electrical systems and are not compatible with High Resistance Grounding for electrical systems. On a HRG
system, L-G voltage rises to the rated line voltage during a bolted ground fault. At this voltage the TVSS which is expecting
to see a Line to Neutral Voltage would read a Line to Line Voltage across it, which would stress the TVSS and eventually
cause the TVSS to fail.
Ordering Notes
1)
Order if additional surge suppression is required.
2)
A wire harness is factory connected to Form-C relay contacts located on each surge suppression assembly for remote
monitoring. Connect the wire harness to the controller’s binary inputs. The controller then provides alarm display
messages and an audible alarm when a surge suppression assembly activates.
List 38: Surge Suppression for 480 VAC Input
Features
♦
Provides two (2) surge suppression assemblies for the power only bay. One wired to rectifier AC input circuit breakers
CB1, CB3, CB5, CB7, and CB9. The other to CB2, CB4, CB6, CB8, and CB10.
♦
100kA interrupting capacity.
♦
Overcurrent fusing and thermal protection.
Restrictions
See