Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 113
(A)
Power/Distribution Bay and Distribution Only Bay: This power board is UL Listed ("c UL") as a DC Power
Distribution Center for Communications Equipment. This unit meets the requirements of CSA 22.2, No. 225
and is tested and Certified by UL ("c UL") as a Custom Built Power Distribution Center for Communications
Equipment.
(B)
Power Only Bay: This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Listed as a power supply for use in Telephone, Electronic Data Processing or Information
Processing Equipment.
1.3.2
NEBS Compliance (pending for Lists 101-132): Compliance verified by a Nationally Recognized Testing Laboratory
(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Vertiv for NEBS compliance reports.
In order to remain compliant during a fan failure condition, the backup battery connection must be utilized to
provide sufficient power to the loads for up to eight (8) hours when the system is operated at greater than 50%
output power. If no backup battery connection is used, the system must operate with a redundant module
installed.
1.4
Local Controls and Indicators
1.4.1
"Bay Alarm" Indicator: Located at the top center of each bay.
Green = OK
Red = Bay Failure
Yellow (flashing) = Identified by the controller
1.4.2
"Distribution Bus" Indicators: Each distribution bus contains and indicator located on a hinged door panel covering
the bus's controller monitoring circuit card.
Green = OK
Red = Card Failure
Yellow (flashing) = Identified by the controller
1.4.3
See also specifications for rectifier, MCA, LMS, and NCU.
2.
DC DISTRIBUTION
2.1
Ratings
2.1.1
Power/Distribution Bay
(A)
Power/Distribution Bay:
2400 amperes, maximum, per bay.
16,000 amperes, maximum, per system.
(B)
Distribution Bus:
1200 amperes, maximum.
Each Power/Distribution Bay has two (2) Distribution Buses.
(C)
Fuse/Circuit Breaker Mounting Positions: Each distribution bus contains 24 fuse/circuit breaker mounting
positions which provides 48 fuse/circuit breaker mounting positions per bay. Note that some fuse/circuit
breaker combinations require more than one fuse/circuit breaker mounting position. Refer to
under
ACCESSORY DESCRIPTIONS
for details.
2.1.2
Distribution Only Bay
(A)
Distribution Only Bay:
6000 amperes, maximum, per bay.
16,000 amperes, maximum, per system.
(B)
Distribution Bus:
1500 amperes, maximum.
Each bay has four (4) Distribution Buses.
(C)
Optional Distribution Panel:
500 amperes, maximum.
One optional Distribution Panel per Distribution Bay.
(D)
Fuse/Circuit Breaker Mounting Positions: Each distribution bus contains 12 fuse/circuit breaker mounting
positions which provide 48 fuse/circuit breaker mounting positions per bay. Note that some fuse/circuit
breaker combinations require more than one fuse/circuit breaker mounting position. Refer to
under
ACCESSORY DESCRIPTIONS
for details.
The optional distribution panel provides twenty-four (24) bullet nose device positions. The panel accepts a
choice of TLS/TPS-type fuseholders or bullet nose-type circuit breakers. When installed, bay can be loaded
with up to (46) 218 circuit breakers or TPL fuses, and (24) bullet nose circuit breakers or TLS/TPS fuses.
Note: The List C Circuit Breaker/Fuse Panel requires distribution position #12 in the Bus #1 Distribution
Panel. Also, distribution position #36 in the Bus #3 Distribution Panel must remain empty.