External Alarm, Reference, and Control Wire Sizes - Power/Distribution and Power Only Bays (List 101, 102, 103, 104, 105)
Recommended External Alarm, Reference, Monitoring, and Control Wire Sizes
Recommended wire size is 22 AWG for loop lengths up to 200 ft. and 18-20 AWG for loop lengths over 200 ft.
External Alarm, Reference, Monitoring, and Control Connections Primary Bay Overview Illustration
Control Shelf
Primary Power/Distribution Bay
Primary Power Only Bay Similar
Front door removed in illustration for clarity only.
Primary Bay Control Shelf
Ethernet Port (NCU)
(Front Door Display)
TB2
(for future use)
TB1
RS-485 Port 1 / Port 2
TB1-1 RS485_1A
TB1-2 RS485_1B
TB1-3 C_GND
TB1-4 RS485_2A
TB1-5 RS485 2B
1
5
TB1
TB2
CAN Port
(to supplemental bay)
10Base-T Ethernet Port (IB4 Board)
(Local Area Network)
NCU
Controller
IB2
Controller
Interface Board
EIB
Controller Extended
Interface Board
USB Port
F1
Power to
Distr. DSM
(3A)
F2
Power to
Touch
Screen
(1-1/3A)
South Bound Port
North Bound Port