![Vertiv NetSure
7100 Series Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/vertiv/netsure-7100-series/netsure-7100-series_installation-manual_1007935063.webp)
Vertiv
|
NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
63
Figure 30:
Installing a GJ/218 Circuit Breaker (1-Pole) (Lists AC, AD, BC, BD) (cont’d on next page)
1/4" Hardened
Flat Washer
1/4" Belleville
Lock Washer
1/4-20 x 3/4” Bolt
(2 places)
Torque to 60 in-lbs.
OFF
ON
Apply anti-oxidizing compound to busbar mating
surfaces before mounting circuit breakers.
INSTALLING CIRCUIT BREAKER
Alarm jumper connector.
Holes to route shunt jumper through (if applicable).
ALARM WIRING (BREAKERS W/OUT SHUNTS)
ALARM WIRING (BREAKERS WITH SHUNTS)
Standard and
Electrical
Trip Breaker
Shunted Breaker Jumper: Red
Alarm Jumper: Brown
Alarm Jumper: Brown
Alarm Jumper: Red
Alarm Jumper: Red
Shunted Breaker Jumper: Black
INSTALLING CIRCUIT BREAKER GUARD
ON
OFF
LONGER SIDE OF GUARD
10-32 X 7/16 PH
10-32 LW
CIRCUIT BREAKER GUARD LABEL
CIRCUIT BREAKER GUARD
TYPICAL DIST ASSY
SHOWN FOR EXAMPLE