NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
71
IB2 (Controller Interface Board) Connections
(if required)
The IB2 (Controller Interface Board) provides connection points for digital inputs, programmable relay outputs,
and temperature probes. The IB2 interface board is mounted inside the distribution cabinet. Refer to
Digital Inputs and Programmable Relay Outputs
Digital input and relay output leads are connected to screw-type terminal blocks located on the IB2.
Recommended torque for these connections is 2.2 in-lbs. Refer to
for terminal locations. Refer to
and
Digital Inputs
Connect up to eight (8) digital inputs to the IB2. Note that you must supply both paths for the digital input
(either a positive or negative signal and the opposite polarity return path). Observe proper polarity. Refer to
for terminal locations and
NOTE!
+24V is factory wired to the Digital Input #8 (+) terminal for your convenience and function
predefined for ESTOP. Customer-furnished system ground applied to terminal Digital Input #8 (-)
activates the ESTOP function. The ESTOP function shuts down and locks out the rectifiers, opens the
LVD’s, and shuts down the converters. When the ESTOP signal is removed, LVD’s close (if battery
present) and converters restart. To restart the rectifiers; turn AC power to the rectifiers OFF, wait 30
seconds or more (until the LEDs on the module extinguish), then turn AC power to the rectifiers ON.
The digital inputs can be programmed to provide an alarm when the signal is applied (HIGH) or removed
(LOW). Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for programming
information.
Digital Input Ratings: Refer to the following.
a)
Maximum Voltage Rating: 60V DC.
b)
Active High: > 19V DC.
c)
Active Low: < 1V DC.
The digital inputs may be preprogrammed for specific functions. Refer to the configuration drawing (C-
drawing) supplied with your system for your system’s specific configuration.
Programmable Relay Outputs
The IB2 provides eight (8) programmable alarm relays with dry Form-C contacts. Connect up to eight (8) relay
outputs to the IB2. Refer to
NOTE!
The relay assigned to “Critical Summary” alarm will operate in the “Fail Safe Mode”. “Fail Safe
Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts between the C
and NO terminals, and closing the contacts between the C and NC terminals.
The remaining 7 relays energize during an alarm condition, closing the contacts between the C and NO
terminals, and opening the contacts between the C and NC terminals.
Refer to the ACU+ Instructions (UM1M820BNA) or NCU Instructions (UM1M830BNA) for programming
information.