Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
44
CO Ground Connection
Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.
A CO ground lead terminated in a two-hole lug can be connected as shown in
NOTE!
10-32 studs (w/hardware) on 5/8" centers are provided for this connection. Note that one stud is
used to secure lug, the other is used for anti-rotation. Recommended torque is 20 in-lbs when using the
supplied hardware.
Battery Connections
DANGER!
Although battery voltage is not hazardously high, the battery can deliver large amounts of
current. Exercise extreme caution not to inadvertently contact or have any tool inadvertently contact a
battery terminal or exposed wire connected to a battery terminal. NEVER allow a metal object, such as a
tool, to contact more than one termination at a time, or to simultaneously contact a termination and a
grounded object. Even a momentary short circuit can cause explosion and injury. Remove watches,
rings, or other jewelry before connecting battery leads. Make the DC (battery) connections last. Make
all other electrical connections without DC input power applied to the system.
DANGER!
Ensure correct polarity when connecting battery leads.
To Battery Busbars
Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located inside
the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the shelf and
are accessible from the front of the shelf. Refer to
. Observe proper polarity when connecting leads.
NOTE!
1/4-20 studs (w/hardware) on 5/8" centers are provided for these connections. Both studs are
used on Lists 2 and 6. Recommended torque is 84 in lbs when using the supplied hardware.
To Bullet Nose-Type Circuit Breaker Positions (Lists BA and NA)
Battery and battery return leads terminated in two-hole lugs are connected as shown in
. Observe
proper polarity when connecting leads.
NOTE!
10-32 studs (w/hardware) on 5/8" centers are provided for these connections. Recommended
torque is 20 in-lbs when using the supplied hardware.
Содержание NetSure 502NGFB Series
Страница 10: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 10 This page is intentionally blank ...
Страница 37: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 37 Figure 14 Controller RJ 45 Ethernet Port ...
Страница 45: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 45 Figure 20 Battery Connections ...
Страница 85: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 85 This page is intentionally blank ...
Страница 86: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA Section 6009 RZ 2020 ...