Table 3:
Programmable Relay Assignments (Factory Default)
Programmable
Relay Output
IB2 Pin No.
Alarm Cable
Color Scheme
Alarms Assigned to this
Relay (Default)
Alarms Assigned to
this Relay (Custom)
1 *
NO
J6-5
W-BL
SCU+: Any Major Alarm
NCU or ACU+: Any
Critical Alarm
COM
J6-3
BL-W
NC
J6-1
W-O
2
NO
J6-6
O-W
SCU+: Any Minor Alarm
NCU or ACU+: Any Major
Alarm
COM
J6-4
W-G
NC
J6-2
G-W
3
NO
J7-5
W-BR
DC Volt High #1
COM
J7-3
BR-W
NC
J7-1
W-S
4
NO
J7-6
S-W
Batt Discharge
DC Volt Low #1
COM
J7-4
R-BL
NC
J7-2
BL-R
5
NO
J8-5
R-O
DC Volt Low #2
COM
J8-3
O-R
NC
J8-1
R-G
6
NO
J8-6
G-R
AC Failure
COM
J8-4
R-BR
NC
J8-2
BR-R
7
NO
J9-5
R-S
Fuse Alarm
COM
J9-3
S-R
NC
J9-1
BK-BL
8
NO
J9-6
BL-BK
Load Share Alarm
Rect No Response
Rect HVSD
Rect AC Fail
Rect Failure
Rect Protect
Rect Fan Fail
Rect Derated
Rect Temp Alarm
COM
J9-4
BK-O
NC
J9-2
O-BK
NOTE!
* The controller relay assigned to “Critical Summary” (NCU or ACU+) alarm or “Major Summary”
(SCU+) alarm (relay 1 by default) will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is
de-energized during an alarm condition, opening the contacts between the C and NO terminals, and
closing the contacts between the C and NC terminals.
The remaining 7 relays energize during an alarm condition, closing the contacts between the C and NO
terminals, and opening the contacts between the C and NC terminals.
ALERT!
All conductors in the Alarm Cable may be connected within the cabinet. Shorting or grounding
of unused conductors may result in service interruption or equipment damage. Therefore insulate all
conductor ends not being used in your application.
Содержание NetSure 502NGFB Series
Страница 10: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 10 This page is intentionally blank ...
Страница 37: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 37 Figure 14 Controller RJ 45 Ethernet Port ...
Страница 45: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 45 Figure 20 Battery Connections ...
Страница 85: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 85 This page is intentionally blank ...
Страница 86: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA Section 6009 RZ 2020 ...