11 PREVENTIVE MAINTENANCE WORKSHEET
Source: DPN002955, Rev. 2
Inspection Date
Job Name
Indoor Unit Model #
Indoor Unit Serial Number #
Room Temperature/Humidity
°
%
Cooling Module #
Good maintenance practices are essential to minimizing operation cost and maximizing product life. Read and follow all
applicable maintenance checks listed below. At a minimum these checks should be performed semi-annually. However,
maintenance intervals may need to be more frequent based on site-specific conditions. Review the unit user manual for
further information on unit operation. Vertiv recommends the use of trained and authorized service personnel, extended
service contracts, and factory certified replacement parts. Contact your local Vertiv Representative for more details.
Cabinet and Coil
1.
Wipe inlet and out grills clean.
2.
Wipe fans and fan inlets clean.
3.
Verify coil is clean.
Electrical Panel
1.
Check fuses.
2.
Check/re-torque wire connections.
Controls
1.
Check/verify control operation (sequence).
2.
Check/test changeover devices (if equipped).
3.
Check/test water detection devices (if equipped).
Pump
1.
Check for pump motor bearing noise.
2.
Verify pump suction pressure is above 10 ps.
Suction:
3.
Pump amp draw
#1
L1
L2
L3
#2
L1
L2
L3
4. Verify pump changeover (if multiple pumps).
11 Preventive Maintenance Worksheet
49
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...