Figure 9.2 Liebert XDH model number nomenclature
Models
XDO16BK
1
XDO16SK
1
(60Hz)
XDO16BS
1
XDO16SS
1
(60Hz)
XDO16BS
1
XDO16SS
1
(50Hz)
Cooling Capacity
Nominal (85°F [29.4°C] EAT): 16kW / 4.5 Tons
Maximum (90°F [32°C] EAT): 17.3 kW / 4.9 Tons
Nominal (85°F [29.4°C] EAT): 14kW/4.0Tons
Maximum (93°F [34°C] EAT): 17.3 kW / 4.9
Tons
Conditions
Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point
Electrical Requirements
Input Voltage
1ph-60Hz-120V
1ph-60Hz-240V
1ph-50Hz-240V
Input Power Connections
Terminal blocks provided internal to module
Full Load Amps
2.7A @ 120V
1.50 @ 230V
1.50 @ 230V
Wire Size Amps
3.4
2.0
2.0
Overcurrent Protection Device
15
15
15
Power consumption,
nominal, watts
335
350
350
Dimensions, inches (mm)
Length
72-1/4 (1835)
Width
24-1/8 (613)
Height
22-1/2 (572) not including electrical and piping access
Weight, lb (kg)
Module only
150 (68)
Shipping weight
238 (108)
296 (134)
Installed, with refrigerant, without options
155 (70)
Number of Fans
1
1
1
Airflow, Nominal, ft3/ min (m3/ hr)
2700 (4587)
2250 (3822)
Audible Noise
85 dBa sound power
83 dBa sound power
Pipe Connections
Refrigerant Supply
from Liebert XDP/Liebert XDC
1/2" OD, Copper
Table 9.4 Liebert XDO16 specifications
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
186
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......