Vertiv | Liebert PEX+Chilled Water | User Manual
66
iCOM Controller Operation
Figure 4-9 Networking of the Multiple Units
4.10. Teamwork Modes
Following are the teamwork modes to group Liebert PEX+CW units in a network
• No Teamwork
• Teamwork Mode 1
• Teamwork Mode 2
• Teamwork Mode 3
All Liebert iCOM controlled cooling units in a network must be set to run in the same teamwork mode
4.10.1. Application of Teamwork Modes
• No Teamwork: Multiple zones in one room
All cooling units work independently, responding to their own sensors. Standby function and unit rotation are
possible, but cascading is not possible (refer
Section 4.10.3
Standby and Cascade). Auto set will not adjust the
proportional band in this mode.