500-750kVA UPS Installation Manual |
62
Table 18
Recommended conduit and cable sizes
Rectifier Input
UPS
Rating
Voltag
e
(VAC)
(# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground
per conduit
kV
A
kW
Copper Conductors
Aluminum Conductors
50
0
450
480
(3) 3C, 3-500kcmil, #2/0AWG
(3) 3C 3-600kcmil, #4/0AWG
625
562.
5
480
(3) 3C 3-600kcmil, #3/0AWG
(4) 3C 3-500kcmil, 250kcmil
750
675
480
(4) 3C, 3-600kcmil, #4/0AWG
(5) 3C 3-600kcmil, 350kcmil
750
675
575
(4) 3C, 3-600kcmil, #4/0AWG
(5) 3C 3-600kcmil, 350kcmil
750
675
600
(3) 3C, 3-600kcmil, #3/0AWG
(4) 3C 3-500kcmil, 250kcmil
Bypass Input
UPS
Rating
Voltag
e
(VAC)
(# of conduits); size of conduits; #-size of phase cables per conduit;
#-size of neutral cables per conduit; size of cable for ground per conduit
kV
A
kW
Copper Conductors
Aluminum Conductors
50
0
450
480
(3) 4C, 4-600kcmil, 2-250kcmil, #1/0AWG
(4) 3C 4-500kcmil, 2-400kcmil, #3/0AWG
625
562.
5
480
(3) 4C 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C -600kcmil, 2-500kcmil, #4/0AWG
750
675
480
(4) 3.5C, 4-500kcmil, 2-500kcmil, #3/0AWG
(5) 3C 4-500kcmil, 2-500kcmil, 250kcmil
750
675
575
(3) 4C, 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C 4-600kcmil, 2-350kcmil, #4/0AWG
750
675
600
(3) 4C, 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C 4-600kcmil, 2-500kcmil, #4/0AWG
Output
UPS
Rating
Voltag
e
(VAC)
(# of conduits); size of conduits; #-size of phase cables per conduit;
#-size of neutral cables per conduit; size of cable for ground per conduit
kV
A
kW
Copper Conductors
Aluminum Conductors
50
0
450
480
(3) 4C, 4-600kcmil, 2-250kcmil, #1/0AWG
(4) 3C 4-500kcmil, 2-400kcmil, #3/0AWG
625
562.
5
480
(3) 4C 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C -600kcmil, 2-500kcmil, #4/0AWG
750
675
480
(4) 3.5C, 4-500kcmil, 2-500kcmil, #3/0AWG
(5) 3C 4-500kcmil, 2-500kcmil, 250kcmil
750
675
575
(3) 4C, 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C 4-600kcmil, 2-350kcmil, #4/0AWG
750
675
600
(3) 4C, 4-600kcmil, 2-250kcmil, #2/0AWG
(4) 3C 4-600kcmil, 2-500kcmil, #4/0AWG
Battery
UPS
Rating
(# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit
kV
A
kW
Copper Conductors
Aluminum Conductors
50
0
450
(4) 2.5C, 2-500kcmil, #4/0AWG
(5) 2.5C 2-500kcmil, 350kcmil
625
562.
5
(4) 2.5C 2-600kcmil, #4/0AWG
(5) 2.5C 2-600kcmil, 350kcmil
750
675
(5) 3C, 2-600kcmil, 250kcmil
(6) 2.5C 2-600kcmil, 400kcmil
Bonding