Figure 45 Password confirmation incorrect, password change failed
11. After correctly entering and confirming the new password, press the Enter key
several times to back
to the main menu screen.
3.6.1
LCD Parameter Settings
NOTE
The correct password (default: 111111) must be entered before the UPS’s configuration or
parameters can be changed. Vertiv recommends recording the password and storing it in an
accessible location for later retrieval.
Table 9
LCD parameter settings
Menu
Item
Setting Range
Default Setting
Syste
m
Auto restart
Disable, Enable
Enable
Auto restart delay
0 ~ 999 seconds
10; Single unit only
Guaranteed shutdown
Disable, Enable
Disable
Remote control
Disable, Enable
Enable
Remote power on delay
0 ~ 999 seconds
0
Remote shutdown delay
0 ~ 999 seconds
0
Redundant
NO, YES
YES
IT earthing system
Disable, Enable
Disable
Dry contact 1 (Output)
Low battery, On bypass, On battery, UPS fault
Low battery
Dry contact 2 (Output)
Low battery, On bypass, On battery, UPS fault
UPS fault
Dry contact 3 (Input)
Battery mode shutdown, Any mode shutdown,
Maintain mode
Maintain mode
Dry contact 4 (Input)
Battery mode shutdown, Any mode shutdown,
Maintain mode
Maintain mode
En
ter
Содержание Liebert ITA2-08KRT208
Страница 1: ...Liebert ITA2 8 10kVA 60Hz 208 220V Three Phase UPS User Manual...
Страница 40: ...Vertiv Liebert ITA2 User Manual 34 Figure 31 Status page menus...
Страница 42: ...Vertiv Liebert ITA2 User Manual 36 Figure 34 Settings Page menus continued Monitor Pg 2 System Pg 2...
Страница 70: ...Vertiv Liebert ITA2 User Manual 64 NOTES...
Страница 71: ...Vertiv Liebert ITA2 User Manual 65...
Страница 72: ...Vertiv Liebert ITA2 User Manual 66...
Страница 73: ......