Quick Start Fan Analog Output
Fan speed percentage during quicktart operation.
Quick Start Overlap Time
Length of time quick start fan speed overlaps normal fan speeds settings. After fully booted, normal fan speed control
resumes when this time expires.
3.3.3 Automatic Restart after Power Failure
Set the cooling unit to return to the status at which it was operating when input power returns after a power failure. (On if it
was powered on and Off if it was powered off before the failure.)
1.
Touch
, then
>
Options Setup
>
Misc Settings
. The MISC SETTINGS panel displays.
2.
Set
Auto Restart Enable
to
Yes
, and use the slider to set the number of seconds to delay before restart, then
touch
Save
.
Automatic restart is enabled.
•
Touch
Cancel
to discard the changes without saving.
3.3.4 Setting Fan Options
Air flow is adjustable via iCOM manually using a building management system (BMS) or automatically using locally
installed temperature sensors.
NOTE: Thermal management units ship with the factory setting Return Sensor for the temperature-control sensor
and the fan speed control sensor.
1.
Touch
, then
>
Options Setup
>
Fan Settings
. The FAN SETTINGS panel displays.
2.
Make adjustments as needed and click
Save
. The option settings are updated.
•
Touch
Cancel
to discard the changes without saving.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
Fan Settings Options
Air Flow Calibration
Maximum allowed fan output voltage.
Allow Fan Modulation with Comp
Enables/disables fan modulation with compressor operation. Values are:
No: Fan speed ramps to STD when a compressor starts operating.
Yes: Fan speed modulates based on CFF while compressor operates.
3 Service Operation
37
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...