LIEBERT® ICOM CMS
TM
Quick Installation Guide
590-1455-501B / SL-18830_REV1_7-17
1
BEFORE YOU BEGIN:
• Make sure that Ethernet
cables are run to the device.
• Consult your IT administrator
and determine the following
iCOM CMS network settings:
IP Address
_______________________________
Subnet Mask
_______________________________
Default Gateway
_______________________________
DNS Servers
_______________________________
MOUNTING THE DEVICE
Mount the iCOM CMS enclosure
on the thermal-management unit
according to the instructions
included with the kit.
CONNECTING AND
CONFIGURING CMS
1. Connect the
communication cable
Inside the iCOM CMS
enclosure, connect the
communication cable to the
485 port on the CMS control
board (see the illustration to
the right).
2. Connecting the
power cable
Inside the iCOM CMS
enclosure, connect the power
cable to the 24- VAC port on
the CMS control board (see the
illustration to the right).
3. Accessing the
Web User Interface
Using a CAT5 Ethernet cable,
connect a computer to the
Ethernet port on the control
board, and change the network
settings on the computer to
communicate with the control
board as follows:
• Static IP address:
169.254.24.10
• Subnet mask: 255.255.0.0
NOTE:
Only use the Google
Chrome web browser to access the
web UI.
On the computer, open the
Google Chrome Web browser
and enter the IP address of
the control board in the
address bar:
• Default IP address:
169.254.24.7
• Default subnet mask:
255.255.0.0
Log-in to the web UI using the
advanced password: 2210.
iCOM CMS Status Screen
Control Board Connections
1
3
2
BMS 485
Com Port