Vertiv™ Liebert EXS 80kVA UPS User Manual
7 Communication
NOTICE: 1. Ensure that the plug of REPO have been correctly connected to the corresponding Pin
of port J14, and that the REPO cable is connected securely in order to ensure that the REPO is not
activated inadvertently as the result of poor contacts.
2. When the REPO switch at the user-end is triggered, the UPS will generate an alarm and cut off the
output immediately, and the UPS will not return to the normal operating state automatically. At this
point, it is necessary to change the REPO switch state, and switch the UPS on manually.
3. REPO switch is only valid for the specified unit in parallel system.
NOTE 1. We recommend using 0.82 mm
2
~ 0.33 mm
2
signal cable (18AWG~33AWG), the cable length
should not be more than 10m.
2. If the REPO has been configured to trip an electronically controlled circuit breaker switch, after the
REPO has been activated it will be necessary to re-arm the switch before restarting the UPS.
7.3 Connecting Parallel Cables
See
for the connection port.
Refer to
for the connection of parallel cables.
7.4 Connecting LBS Cables
See
for the connection port.
Refer to
for the connection of LBS cables.
Содержание Liebert EXS 80kVA UPS
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Страница 12: ...4 Vertiv Liebert EXS 80kVA UPS User Manual Safety Precaution This page is intentionally left blank...
Страница 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Страница 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Страница 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Страница 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Страница 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...