5 PIPING REQUIREMENTS
All fluid connections to the unit, with the exception of the condensate drain, are sweat copper. Factory-
installed piping brackets must not be removed. Field-installed piping must be installed in accordance with
local codes and must be properly assembled, supported, isolated and insulated. Avoid piping runs
through noise-sensitive areas, such as office walls and conference rooms.
Refer to specific text and detailed diagrams in this manual for other unit-specific piping requirements.
All piping below the elevated floor must be located so that it offers the least resistance to air flow. Careful
planning of the piping layout under the raised floor is required to prevent the air flow from being blocked.
When installing piping on the subfloor, we recommend that the pipes be mounted in a horizontal plane
rather than stacked one above the other. Whenever possible, the pipes should be run parallel to the air
flow.
The pipe connection locations, piping general arrangement and schematics are described in the
submittal documents included in the
The following tables list the relevant documents by number and title.
Document Number
Title
Piping Schematic, Downflow, CW305, 375, 415
Table 5.1 Piping General-arrangment Drawings
Document Number
Title
Connection Locations, Data Hall with horizontal-discharge, Front-left facing
electrical/piping compartment
Connection Locations, Bottom-discharge, Front-right facing electrical/piping
compartment
Connection Locations, Data Hall with horizontal-discharge, Front-right facing
electrical/piping compartment
Connection Locations, Bottom-discharge, Front-left facing electrical/piping compartment
Connection Locations, Gallery with horizontal-discharge, Front-right facing electrical/piping
compartment
Connection Locations, Gallery with horizontal-discharge, Front-right facing electrical/piping
compartment
Table 5.2 Piping Connection Drawings
5 Piping Requirements
23
Содержание Liebert CW
Страница 1: ...Liebert CW Thermal Management System Installer User Guide 305 kW 375 kW 415 kW Capacity 50 60 Hz...
Страница 10: ...Vertiv Liebert CW Installer User Guide 6 This page intentionally left blank...
Страница 24: ...Vertiv Liebert CW Installer User Guide 20 This page intentionally left blank...
Страница 32: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Страница 34: ...Vertiv Liebert CW Installer User Guide 30 This page intentionally left blank...
Страница 36: ...Vertiv Liebert CW Installer User Guide 32 This page intentionally left blank...
Страница 46: ...Vertiv Liebert CW Installer User Guide 42 This page intentionally left blank...
Страница 48: ...Vertiv Liebert CW Installer User Guide 44 This page intentionally left blank...
Страница 75: ...Vertiv Liebert CW Installer User Guide...