5.
Float charge temperature compensation (optional)
This function must be used together with the battery temperature detection device. The Vertiv battery
temperature sensor is a standard option for your selection.
6. EOD protection
When the battery voltage drops to the EOD voltage, the battery converter shuts down automatically and the
battery is inhibited to avoid further battery discharge. The EOD voltage is settable from 1.60 V/cell to 1.90
V/cell (VRLA).
7.
Battery low pre-warning time
The battery low pre-warning time is adjustable between 3 min and 60 min. The default setting is 5 min.
8.
Maximum battery discharge time
When the battery has small current discharge for a long time, the battery is over discharged and even has
unrecoverable damage, thus setting a battery discharge time to protect the battery is essential. The limit of
time setting shall be configured by service engineer through the Vertiv setting software.
9. Maximum boost charge protection time
To protect against the battery overcharge damage caused by long time boost charge, a protect time setting is
essential. The limit of time setting shall be configured by service engineer through the Vertiv setting software.
2.5.2 Advanced Function
The UPS provides battery maintenance test function. At periodic intervals, 20% of the rated capacity of the battery will be
discharged automatically, and the actual three-phase load must exceed 20% of the nominal UPS capacity. If the load is less
than 20%, the automatic discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The battery
maintenance test function can be disabled through the Vertiv setting software.
Conditions: Battery at float charge for at least 5 h, load equal to 20% to 100% of rated UPS capacity.
Trigger: Automatically, or manually through the command of battery maintenance test in touch screen.
Interval: 30 to 360 days (default setting: 60 days).
The UPS also provides battery capacity self-test function: Periodically test the battery activity, test the battery residual
capacity, judge the battery quality, and then provide corresponding measures. The capacity self-test is started by the user
through the touch screen. During the capacity self-test, the battery will continuously discharge to the battery under-voltage
shutdown threshold. After the self-test is finished, the system will update the battery curve table. The capacity self-test
command is valid only one time, without any memory. During the capacity self-test, if the battery maintenance requirement
is satisfied, the system will generate audible/visual alarm and give corresponding records.
Conditions: System load rate is within 20% to 100%, battery float charge at least 5 h, and generator not connected; the
current system is in float charge state.
Trigger: Start up through the touch screen.
N O T E:
1. T h e battery will co n tin u o u sly disch arge to th e battery u n der-vo ltage sh u tdo wn th resh o ld,
th en th e battery tran sfer to th e ch argin g state. W h en th e capacity self-test is fin ish ed, th e
system will u pdate th e battery cu rve table.
2. T h e u ser can m an u ally sto p th e capacity self-test o peratio n th ro u gh th e to u ch screen .
2 Overview
20
Vertiv™ Liebert® APM Plus User Manual
Содержание APM 0250kMK16FN02000
Страница 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Страница 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 16: ...1 Important Safety Instructions 8 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 60: ...4 Electrical Installation 52 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 73: ...Figure 5 11 Customize the display 5 Operator Control and Display Panel 65 Vertiv Liebert APM Plus User Manual...
Страница 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Страница 154: ...Figure 8 8 LBS port J4 on bypass control module 8 Parallel System and LBS System 146 Vertiv Liebert APM Plus User Manual...
Страница 182: ...11 Service and Maintenance 174 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 191: ...Vertiv Liebert APM Plus User Manual...