Vertiv™ NetSure™ +24V Battery Tray Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
8
4
Alarm Jumper Routing
Procedure
NOTE!
as this procedure is performed.
1.
Connect the YELLOW 22GA jumper to “COM” terminal of breaker.
2.
Route jumper up to the next circuit breaker. Refer to
NOTE!
If Alarm jumper is not required or there is no battery tray mounted on top, Ty-rap unsed jumper back onto the
harness.
3.
Connect stripped end of alarm jumper into power system’s fuse alarm input connection point.
NOTE!
For the Vertiv™ Vortex™ or Vertiv™ NetSure™ 700 system, this is PIN 11 of TB1 (System Fuse Alarm Input) on the
Interconnect/Inhibit Card on the right side of the base of the power system distribution cabinet.
For Vertiv™ NetSure™ 710
system this is PIN 1 of TB1 (Battery Tray FA) on the System Interface circuit card inside the distribution cabinet.
Verify that
when the battery disconnect breaker is turned off, the controller generates a FA alarm.