Vertiv | Liebert EXS 80kVA UPS | User Manual
100
Maintenance
To ensure the battery life, it is required to:
• Keep the ambient temperature ranging from 15 °C to 25 °C.
• Prevent small current discharge. Continuous battery operation time exceeding 24 hours is strictly prohibited.
•
Charge the battery for at least 12 hours, if the battery hasn’t been charged for three months at specified
ambient temperature, or two months at high ambient temperature.
• Check the battery connection screws on regular intervals, and re-tighten them if necessary.
• Ensure that all the safety devices are present in good condition and that they function correctly, and
make sure that the battery management parameter settings are correct.
• Measure and log the ambient temperature in the battery room.
• Check whether the battery ports are damaged or hot, and check the condition of the chassis and the
covers.
If any of the batteries leaks, place them in a suitable container and dispose them in accordance with local
regulations.
Lead-acid batteries are classified as hazardous waste material. The control of waste battery pollution is a
nationally important issue. Batteries must be stored, transported, used and disposed in accordance with national
and local legal requirements and all other criteria applicable to the treatment of hazardous waste material and
waste battery pollution prevention.
According to the applicable regulations, waste lead-acid batteries must be recycled, while all other disposal
methods are prohibited. Uncontrolled or random disposal of lead-acid waste batteries, or other improper disposal
methods can result in serious environmental pollution, which the relevant authorities will investigate.
As the provider of lead-acid batteries, Vertiv has developed a dedicated service network and waste battery
recycling system to assist users to legally dispose of waste batteries. Contact Vertiv or your nearest service
center for detailed information about the waste battery the recycling system.
Vertiv can not be held responsible for the environmental impact resulting from the non- compliance with the
guidelines set out in this section or from the use waste battery recycling system offered by Vertiv.
8.3. Cleaning UPS
To ensure free airflow inside the UPS: Clean the UPS periodically, especially the ventilation holes. If necessary,
clean the UPS with a vacuum cleaner. Confirm that the ventilation holes are unobstructed.
Содержание EXS 0080kTK16FN01000
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...This page is intentionally left blank...
Страница 46: ...Vertiv Liebert EXS 80kVA UPS User Manual 32 This page is intentionally left blank...
Страница 66: ...Vertiv Liebert EXS 80kVA UPS User Manual 52 This page is intentionally left blank...
Страница 102: ...Vertiv Liebert EXS 80kVA UPS User Manual 88 This page is intentionally left blank...
Страница 112: ...Vertiv Liebert EXS 80kVA UPS User Manual 98 This page is intentionally left blank...
Страница 116: ...Vertiv Liebert EXS 80kVA UPS User Manual 102 This page is intentionally left blank...
Страница 124: ...Vertiv Liebert EXS 80kVA UPS User Manual 110 This page is intentionally left blank...
Страница 128: ...Vertiv Liebert EXS 80kVA UPS User Manual 114 This page is intentionally left blank...
Страница 134: ...Vertiv Liebert EXS 80kVA UPS User Manual 120 This page is intentionally left blank...
Страница 136: ...Vertiv Liebert EXS 80kVA UPS User Manual 122 This page is intentionally left blank...