background image

19

Save  These  Instructions                                                                                                                             

Vermont Castings  •  Aspen 1920 Owner's Manual_R32 • 08/17

Figure 5.9

 - Wall Pass-through with ventilated steel thimble.

ST275

wall with

ventilated

steel thimble

24 ga. Sheet 

Steel Supports 

24 ga. Sheet 

Steel Supports 

2” (51mm) Min.

Chimney clearance to sheet steel 

supports and combustibles

2” (51mm) 

Min.

Chimney Flue

2” (51mm) Min.

air space

Prefab 

Chimney

Section

Prefab Chimney

Section

Chimney 
Connector

Masonry Chimney 

constructed to NFPA 211

Figure 5.8

 - Wall Pass-through using single wall chimney connector 

with a ventilated steel thimble.

ST274

single wall 

w/ventilated thimble

12/99

Min. 6” 

(152mm) 

Chimney clearance to sheet   

steel supports and combustibles

2” (51mm) Min.

Glass Fiber 

Insulation

Chimney Connector

Chimney Flue

Steel Thimble

 with two 

1” (25mm) Ventilated 

Channels 

Masonry Chimney 

constructed to NFPA 211

24 ga. Sheet 

Steel Supports 

Figure 5.10

 - CSA approved Wall Pass-through.

ST276

CSA approved wall 

pass-through

12/99

24 ga. Sheet 

Steel Support 

24 ga. Sheet 

Steel Support

(one side only) 

Min. 18” 

(460mm) 

Chimney clearance to sheet steel 

supports and combustibles

2” (51mm) 

Min.

Chimney Flue

Chimney

Connector

Masonry Chimney constructed 

to CAN/CSA-B365

Min. 18” 

(460mm) 

Figure 5.7

 - Wall Pass-through using factory-built insulated chimney 

section.

ST273

nfpa 

factory built insulated

chimney section

12/99

Min. 9” 

(230mm) 

Air Space

Min. 9”

230mm 

Chimney Flue

Sheet Steel 

Supports

Min. 2” (51mm) 

Non-soluble 

refractory cement

Solid insulated, listed factory-built 

chimney length set flush with flue

Chimney 

Connector

Masonry 

Chimney 

constructed 

to NFPA 211

24 ga. Sheet 

Steel Supports 

Canadian Requirements:

In Canada, the Canadian Standards Association has 

established specific guidelines regarding wall pass-though 

design. Figure 5.10 shows one approved method in which 

all combustible material in the wall is cut away to provide 

the required 18” (457 mm) clearance around the connector. 

The  resulting  space  must  remain  empty. A  flush-mounted 

sheet metal cover may be used on one side only. If covers 

must be used on both sides, each cover must be mounted 

on noncombustible spacers at least 1” (25 mm) clear of the 

wall. Your local dealer or your local building inspector can 

provide details of other approved methods of passing a 

chimney connector through a combustible wall.

In Canada, this type of installation must conform to CAN/

CSA-B365, Installation Code for Solid Fuel Burning 

Appliances and Equipment.  

Alternate methods approved by the NFPA: 

•  Using a section of double-wall chimney with a 9” (229 

mm) clearance to combustibles. (Figure 5.7)

•  Placing a chimney connector pipe inside a steel double-

wall ventilated thimble, which is then separated from 

combustibles  by  6”  (152  mm)  of  fiberglass  insulating 

material. (Figure 5.8)

•  Placing a chimney connector pipe inside a section of 9” 

(229 mm) diameter, solid-insulated, factory-built chimney, 

with two inches of air space between the chimney section 

and combustibles. (Figure 5.9)

Содержание The Aspen 1920

Страница 1: ...N HOT WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL IT IS COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS KEEP CHILDREN AWAY CAREFULLY SUPERVISE CHILDREN IN SAME ROOM AS FIREPLACE ALERT CHILDREN AND ADULTS TO...

Страница 2: ...hacombustiblewallorceiling Floor Protection U S With Vermont Castings Bottom Heat Shield Kit No 1895 use a noncombustible floor protector such as1 4 non asbestosmineralboardorequivalentor24gaugesheetm...

Страница 3: ...ction 13 5 Chimneys and Venting A Draft 14 B Chimney Connectors 14 C Wall Pass throughs 14 D The Chimney 15 6 Mobile Home US Only A Mobile Home Installation 20 7 Appliance Set Up A Un Pack Stove 21 B...

Страница 4: ...manner inconsistent with operating instructions in this manual Area Heated 400 1 200 Square feet Loading Front Chimney Connector 6 152 mm Flue Exit Position Reversible top or rear Primary Air Manually...

Страница 5: ...S ROOM HEATER IS NOT PROPERLY INSTALLED AHOUSEFIREMAYRESULT TOREDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION...

Страница 6: ...d clearances to combustibles Insulation must not touch the chimney You must maintain the designated air space around the chimney This space around a chimney is necessary to allow natural heat removal...

Страница 7: ...t all items for shipping damage Notify dealer of any missing or damaged goods 2 All safety warnings have been read and followed precisely 3 This Owner s Manual has been read in it s entirety 4 Floor p...

Страница 8: ...s Manual_R32 08 17 15 381 mm 24 610 mm Top Exit Flue Collar Height 16 406 mm 22 570 mm 7 184 mm 18 457 mm 23 584 mm C L 6 152 mm 7 191 mm 3069 Aspen Specs 2 15 00 djt 22 565 mm Figure 4 1 Aspen 1920 s...

Страница 9: ...Top Exit Rear H S Double Wall Connector Shields 1 3 Q 24 610 mm R 7 178 mm S 13 330 mm T 16 406 mm U 7 178 mm V 8 203 mm Chimney Connector Unprotected Surface Vertical Protected Surface Vertical No H...

Страница 10: ...all Stove in Corner Stove Installed Parallel to Wall Stove in Corner ST255 exit diagram 12 15 99 djt S B C C D E F J K NA NA O R N M Q A H I U P V T S G Top Exit No Heat Shields Rear Exit Rear Heat Sh...

Страница 11: ...hind connector Parallel installation with rear wall pass through two wall shields Figure 4 6 Reduced clearances for both rear and side walls Wall shields may meet at corner if desired Shielding for co...

Страница 12: ...of the stove and the decorative side trim on the fireplace face and the top of the stove and the mantel Maximum Mantel depth A Figure 4 8 of a combustible mantel is 9 230 mm At that depth the clearanc...

Страница 13: ...bottom plate of your Aspen The floor area directly under and around the stove will require protection from radiant heat as well as from stray sparks or embers that may escape the firebox Heat protecti...

Страница 14: ...connector may pass through an attic or roof space closet or other concealed space or through a floor or ceiling Whenever possible avoid passing the connector through a combustible wall if you must us...

Страница 15: ...SANDINSTALLATIONINSPECTION REQUIREMENTS IN YOUR AREA Before you begin an installation review your plans to be certain that Your stove and chimney connector will be far enough from combustible material...

Страница 16: ...lp assure safety use chimney components manufactured by a single source NOTE For installations using double wall connectors minimum clearances must conform to those listed in the clearance chart in Se...

Страница 17: ...e chimney Single wall Chimney Connectors Beginning at the flue collar of the stove assemble the chimney connector Insert the first crimped end into the stove s flue collar and keep each crimped end po...

Страница 18: ...d States for passing chimney connectors through combustible walls Many building code inspectors follow these guidelines Figure 5 6 shows one NFPA approved method All combustible material in the wall i...

Страница 19: ...ney Flue Sheet Steel Supports Min 2 51mm Non soluble refractory cement Solid insulated listed factory built chimney length set flush with flue Chimney Connector Masonry Chimney constructed to NFPA 211...

Страница 20: ...ding Heating Appliances UL 103 5 The chimney must be attached directly to the stove and must extend at least 3 914mm above the part of the roof through which it passes The top of the chimney must exte...

Страница 21: ...g brackets from the stove bottom DO NOT discard washers 2 Install two legs using the hex head bolts in the hardware pack along with the 3 8 washers that were used to hold the brackets in place The sho...

Страница 22: ...into the flue collar Using the holes in the collar as guides drill 1 8 3mm holes through the connector pipe Use the three 10 x 1 2 sheet metal screws provided to secure the chimney connection to the f...

Страница 23: ...you will ensure proper draft and gain maximum efficiency and enjoyment from your stove Do not alter the position of the andirons Building a fire too close to the glass may cause damage to the glass cr...

Страница 24: ...raws air into the stove for combustion A slow lazy fire with the stove s air inlets fully open indicates a weak draft A brisk fire supported only by air entering the stove through the normal inlets in...

Страница 25: ...flow will lower flue temperatures reduce draft strength and promote creosote development overall stove performance will suffer The effect is similar to that of a vacuum cleaner with a hole in the hos...

Страница 26: ...also depends on a sufficient supply of air to the stove The chimney cannot pull more air than is available Sluggish draft can be caused by a house that is tight enough to prevent the ready flow of air...

Страница 27: ...ward the back of the stove light them and close the door This should heat the chimney enough to initiate strong draft Once the draft is established open the front door and light the rest of the fuel b...

Страница 28: ...itintheclosedcontaineruntilallcindershavethoroughly cooled You can use wood ash as a garden fertilizer CAUTION Never use your household or shop vacuum cleaner to remove ash from the stove always remov...

Страница 29: ...ure the glass is completely cool Clean the glass with water or a cleaner made especially for this purpose Do not use abrasive cleaners Rinse the glass thoroughly Dry the glass completely Glass Replace...

Страница 30: ...and the stove has cooled Be sure to follow the standard safety procedure for working with dusty materials Wear safety goggles and a dust mask Step 1 Remove the existing gasket by grasping an end and p...

Страница 31: ...e system if necessary Failure to keep the chimney and connector system clean can result in a serious chimney fire When wood is burned slowly it produces tar organic vapors and moisture that combine to...

Страница 32: ...3 11 43 36 42 37 33 21 12 41 20 19 50 38 47 21 35 41 13 44 38 51 6 5 51 19 40 17 18 3 51 38 41 2 50 53 38 50 22 28 45 25 46 54 0369 Aspen 1920 parts 8 02 55 56 57 Vermont Castings reserves the right t...

Страница 33: ...ver 30000351 30006800 Front 30000348 30006801 Ashlip 30000352 30006808 Door 300003350 30006802 Leg Set of Four 30000502 30006810 Single Leg 30000360 30006807 Item Description Part number 30 Glass Gask...

Страница 34: ...occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier However the warranty shall commence no later than 24...

Страница 35: ...nce some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints...

Страница 36: ...but not limited to improper chimney or venting installation LIMITATIONS OF LIABILITY The owner s exclusive remedy and HHT s sole obligation under this warranty under any other warranty express or imp...

Страница 37: ...37 Save These Instructions Vermont Castings Aspen 1920 Owner s Manual_R32 08 17...

Страница 38: ...38 Save These Instructions Vermont Castings Aspen 1920 Owner s Manual_R32 08 17 352 Mountain House Road Halifax PA 17032 www vermontcastings com...

Отзывы: