15
Save These Instructions
Vermont Castings • Aspen 1920 Owner's Manual_R32 • 08/17
Figure 5.1
- The 2'-3'-10' Chimney Rule.
2' Min.
2' Min.
3'
Min.
0 To 10'
3'
Min.
0 To 10'
AC617
RLTSKC8
2/11/98
Reference Point
Figure 5.2 -
Standard Chimney Types
ST241
chimney types
12/13/99 djt
A prefabricated double-
wall insulated chimney
A tile-lined
masonry
chimney
Masonry Chimneys:
An existing masonry chimney must be inspected to confirm
that it has a lining. Do not use an unlined chimney. The
chimney also should be examined for cracks, loose mortar,
other signs of deterioration, and blockage. Repair any defects
before the chimney is used with your stove.
Chimneys:
Your stove must be connected either to a sound masonry
chimney that meets local codes, to a relined masonry chimney
that meets local codes, or to an approved prefabricated metal
chimney. Whichever of those types you use, the chimney and
chimney connector must be in good condition and kept clean.
If you use an existing masonry chimney, it must be inspected
to ensure safe condition before the stove is installed. Your
local professional chimney sweep, building inspector, or fire
department official will be able to make the inspection or
direct you to someone who can.
The chimney should extend at least 3' (914 mm) above the
highest point where it passes through a roof, and at least
2' (610 mm) higher than any portion of a building within 10'
(3 m).
To assure proper draft and good performance, any chimney
used with this stove should extend at least 16' (4.9 m) above
the flue collar of the stove.
D. The Chimney
SAFETY NOTICE: IF YOUR STOVE IS NOT PROPERLY
INSTALLED, OPERATED AND MAINTAINED, A HOUSE
FIRE MAY RESULT. FOR SAFETY, FOLLOW ALL
INSTALLATION, OPERATION AND MAINTENANCE
DIRECTIONS. CONTACT LOCAL BUILDING OFFICIALS
ABOUT RESTRICTIONS AND INSTALLATION INSPECTION
REQUIREMENTS IN YOUR AREA.
Before you begin an installation, review your plans to be
certain that:
•
Your stove and chimney connector will be far enough from
combustible material to meet all clearance requirements.
•
The floor protector is large enough and is constructed
properly to meet all requirements.
•
You have all necessary permits from local authorities.
Your local building official is the final authority for approving
your installation as safe and determining that it meets local
and state codes.
The metal label permanently attached to the back of the
stove indicates that the Aspen has been tested to current UL
and ULC standards by Intertek Testing Services of Middleton,
Wisconsin. Clearance and installation information is also
printed on the label. Local authorities generally will accept the
label as evidence that, when the stove is installed according to
the information on the label and in this manual, the installation
meets codes and can be approved. Codes, however, vary in
different areas. Before starting the installation, review your
plans with the local building authority. Your local dealer can
provide any additional information needed.
For any unresolved questions about installation, refer to the
National Fire Protection Association’s publication ANSI/NFPA
211–1988 Standard for Chimneys, Fireplaces, Vents and
Solid Fuel Burning Appliances. In Canada, the equivalent
publication is CSA CAN-B365, Installation Code for Solid
Fuel Burning Appliances and Equipment. These standards
are the bases for many national codes. They are nationally
recognized and are accepted by most local authorities. Your
local dealer or your local building official may have a copy
of these regulations.
IMPORTANT: Failure to follow these installation
instructions may result in a dangerous situation,
including a chimney or house fire. Follow all instructions
exactly and do not allow makeshift compromises to
endanger property and personal safety.