background image

5

Encore

®

 1450CE Non-Catalytic Woodburning Stove

30003845

what kind of chimney to use

You must connect the Encore to a code-approved 
masonry chimney with a flue liner, to a relined masonry 
chimney that meets local codes, or to a prefabricated 
metal chimney. The chimney and chimney connector 
must be in good condition and kept clean.
If you use an existing masonry chimney, it must be 
inspected to ensure it is in a safe condition before 
the stove is installed. Your local professional chimney 
sweep, building inspector, or fire department official will 
be able to inspect the chimney or provide a referral to 
someone who can.
The flue and chimney design must meet requirement 
J, Part J of the building regulations 000 (Combustion 
Appliances and Fuel Storage Systems).

ST241

chimney types

12/13/99   djt

ST41

A tile-lined 

masonry 

chimney

A prefabricated double-

wall insulated chimney

fig. 3

  Approved chimney types.

masonry chimneys

An inspection of the chimney must confirm that it has 
a lining. Do not use an unlined chimney. The chimney 
should have no cracks, loose mortar, other signs of 
deterioration, and blockage. Repair any defects before 
the chimney is used with your stove.  
Unused openings in an existing masonry chimney must 
be sealed with masonry to the thickness of the chimney 
wall, and the chimney liner should be repaired.  Open-
ings sealed with pie plates or wallpaper are a hazard 
and should be sealed with mortar or refractory cement. 
In the event of a chimney fire, flames and smoke may 
be forced out of these unused thimbles.
The chimney should be thoroughly cleaned before use.
A newly-built masonry chimney must conform to the 
standards of your local building code or, in the absence 
of a local code, to a recognized national code.  Masonry 
chimneys must be lined, either with code-approved 
masonry or pre-cast refractory tiles, stainless steel 
pipe, or a code-approved, “poured-in-place” liner.  The 
chimney’s clean-out door must seal tightly.

prefabricated chimneys

These should be an internal diameter of 150 mm (6”) 
and be of the twin wall insulated construction that has 
been approved for solid fuel use (e.g. Rite Vent ICS of 
ICID Lite Chimney Systems). Diameters over 00 mm 
(8”) are not recommended due to the large cross-sec-
tion causing excessive cooling of the flue gases.  

do Not coNNect thiS uNit to a chimNey flue 
ServiNg aNother appliaNce.

chimney Size

An Encore with an 03 mm (8”) flue collar is approved 
for venting into a masonry chimney with a nominal flue 
size of 03 x 03 mm (8” x 8”) or 03 x 305 mm (8” 
x 1”), and into a round flue with nominal flue size of 
03 mm (8”). An Encore with a 15 mm (6”) flue collar 
is approved for venting into a masonry chimney with a 
nominal flue size of 03 x 03 mm (8” x 8”), and into a 
round flue with nominal flue of 15 mm (6”). 

Note:  when installed with a 152 mm (6”) flue col-
lar, the encore may not be operated with the front 
doors open.

Whatever the flue collar size, an Encore may be vented 
into  larger chimneys as well.  However, chimneys 
with liners larger than 03 x 305 mm (8” x 1”) may 
experience rapid cooling of smoke and reduction in 
draft, especially if the chimneys are located outside the 
home. These large chimneys may need to be insulated 
or have their flues relined for proper stove performance.  
Accessories to help make the connection between 
stainless steel chimney liners and your Encore are 
available through your local dealer.

chimney connector guidelines

A chimney connector is the double-wall or single-wall 
pipe that connects the stove to the chimney. The chim-
ney itself is the masonry or prefabricated structure that 
encloses the flue. Chimney connectors are used only to 
connect the stove to the chimney, as in Figure 5. 

connecting flue pipes

Connector pipes should meet the requirements of the 
building regulations. This can be achieved by the use 
connecting fluepipes included in the following catego-
ries:
a) Vitreous enamelled steel pipe complying with BS 
6999: 1989 (1996);
b) Pipes made from stainless steel as descirbed in BS 
EN 1008-1:1995 grades 1.4401, 1.4404, 1.443 or 
1.4436 with flue wall thickness of at least 1 mm; 
c) Mild steel fluepipes complying with BS 1449: Part 1: 
1991, with a flue wall thickness of at least 3 mm;
d) Cast iron fluepipes complying with BS 41: 1973 
(1998).

Содержание Encore 1450C

Страница 1: ...the risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact local building officials about restrictions and...

Страница 2: ...Vermont Castings stove It also contains useful information on maintenance and assembly of this product We urge you to read the manual thoroughly and to keep it as a reference Sincerely All of us at MH...

Страница 3: ...r 8 oval flue collar 203 mm 8 diameter for optional 6 flue collar 152 mm 6 diameter Chimney flue size for 8 oval flue collar 203 mm 8 minimum for optional 6 flue collar 152 mm 6 minimum Flue exit posi...

Страница 4: ...low all instructions exactly and do not allow makeshift com promises to endanger property and per sonal safety All local regulations including those referring to national and European standards need t...

Страница 5: ...6 and be of the twin wall insulated construction that has been approved for solid fuel use e g Rite Vent ICS of ICID Lite Chimney Systems Diameters over 200 mm 8 are not recommended due to the large...

Страница 6: ...on of chimney connec tor serve as guides when you drill 3 mm 1 8 holes in the bottom of the next section Secure the chimney connector to the chimney In structions for various installations follow Be s...

Страница 7: ...mble sleeve should protrude 25 51 mm 1 2 into the room Fig 6 Use furnace cement and thin gasketing to seal the sleeve in place in the thimble Secure the chimney connector to the outer end of the sleev...

Страница 8: ...675 mm 26 you may install an Encore through the opening using a positive connection kit available from your lo cal dealer These positive connection kits ensure a tight fit between the stove flue colla...

Страница 9: ...clearances of the hearth are as fol lows The constructed hearth should be constructed in ac cordance with the recommendations in document J and should be of minimum width 840 mm and minimum depth 840...

Страница 10: ...o any combustible surfaces e g wooden mantels or lintels and to timber framed studded walls even if they are faced with noncombustible board Detailed information on fireplace and hearth construction i...

Страница 11: ...ces and Fuel Storage Systems This can be achieved by following the recommenda tions of Approved Document J These are as shown in Figure 13 34 FLUEPIPE CLEARANCES D at least 3 x D Elevation Without Shi...

Страница 12: ...no weight on the leg while making the adjustment Reverse the Flue Collar If Necessary Reverse the flue collar by removing the two 2 screws that attach it to the back of the stove Be sure the gas ket...

Страница 13: ...ided with stove under the right wing of the bottom heat shield with two 2 10 sheet metal screws 5 Attach the rheostat to its holder by inserting the rheostat control shaft through the holder hole Inst...

Страница 14: ...Andirons ST636 Fig 19 The Encore controls are conveniently located and easy to operate Door Handle A Single Air Control Regulates Heat Output and Burn Time The primary air control lever located on th...

Страница 15: ...d is their density Hardwoods because of their greater density burn longer than softwoods and can increase the time between refuelings Store wood under cover to keep it dry The longer it is stored in a...

Страница 16: ...far right to 1 3 the distance to left Medium From 1 3 to 2 3 the distance to left High From 2 3 the distance to left to far left DO NOT OPERATE THE STOVE WITH THE ASH DOOR OPEN OPERATION WITH THE ASH...

Страница 17: ...nclude some smaller pieces of wood in the new fuel load to help the stove regain its operating temperature quickly Use this sequence as a guide to successful refueling NOTE Door handles can be hot A g...

Страница 18: ...lly dispersed it should be kept in the closed container until all cinders have thoroughly cooled You can use wood ash as a garden fertilizer CAUTION Never use your household or shop vacuum cleaner to...

Страница 19: ...at heat from the chimney walls will transfer to the house and not be wasted outdoors An indoor chimney will not lose its heat to the outdoors so Draft Management it takes less heat from the stove to h...

Страница 20: ...voiding overly dry wood loaded into a very hot stove may help this problem If back puffing persists contact your dealer or qualified chimney sweep to help diag nose the problem Draft Testing An easy w...

Страница 21: ...not use abrasive cleaners Rinse the glass thoroughly Dry the glass completely Replace Broken Glass Immediately Do not operate your stove if the glass in the doors is damaged If you need to replace th...

Страница 22: ...an end and pulling firmly 2 Use a wire brush or the tip of a screwdriver to clean the channel of any remaining cement or bits of gasket Fig 32 Remove stubborn deposits of cement with a cold chisel if...

Страница 23: ...cantly However regular chimney inspection and maintenance must still be performed For safety good stove performance and to protect your chimney and chimney connector inspect your chimney and chimney c...

Страница 24: ...and remove ash build up behind the com bustion package This should be done in conjunction with annual cleaning of the chimney connector since this inspection is most conveniently done through the flu...

Страница 25: ...64 62 19 56 60 59 22 56 58 54 23 25 48 49 50 45 53 42 41 53 24 28 57 26 27 38 18 17 14 16 46 65 62 44 43 40 39 34 35 70 33 31 32 30 28 42 29 15 71 36 5 6 75 76 77 77 78 27 80 MHSC reserves the right...

Страница 26: ...er Pin Ashdoor 30001749 33 Ashdoor Hinge Lower 30002404 34 Ashpan 1601025 35 Ashpan Bracket 1601039 36 Ashpan Cover 1601027 37 Airwash Manifold 30002407 38 Front See Chart Pg 33 39 Left Door See Chart...

Страница 27: ...0002633 30002623 30002643 30003082 Right Side 30003053 30002612 30004877 30003063 30003073 30002632 30002622 30002642 30003083 Flue Collar 30003008 2324280 30004868 30003020 30003032 2374280 1324280 3...

Страница 28: ...d wood chemically treated wood or any fuel not recommended in the Owners Guide 4 This warranty does not cover a stove repaired by someone other than a Vermont Castings Authorized Dealer 5 Damage to th...

Отзывы: