background image

© CFM Corporation

2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3 

800-668-5323 • www.cfmcorp.com

CFM Corporation

Содержание Defiant 1945CE

Страница 1: ...INSTALLED OPERATED AND MAINTAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR...

Страница 2: ...of warmth beauty and comfort in your home At CFM Corporation we share that joy and appreciation for the hearth We assure you that your cast iron Vermont Castings stove has been made with the utmost c...

Страница 3: ...rior using new technologies for ef cient combustion Americans purchased over a quarter million De ants as they rediscovered the common sense of heating with wood a home grown fuel with none of the pol...

Страница 4: ...N T 826 mm 32 724 mm 28 788 mm 31 96 mm 3 546 mm 21 489 mm 19 464 mm 18 546 mm 21 3841 Defiant EU dimensions 7 06 768 mm 30 D E F I A N T 591 mm 23 489 mm 19 654 mm 25 C L 737 mm 29 Flue exit position...

Страница 5: ...ng a chimney or house re Follow all instruc tions exactly and do not allow makeshift compro mises to endanger property and personal safety All local regulations including those referring to national a...

Страница 6: ...t be operated with the front doors open Whatever the ue collar size an De ant may be vented into larger chimneys as well However chimneys with liners larger than 203 x 305 mm 8 x 12 may experience rap...

Страница 7: ...Flue Gas Direction Toward Stove ST242 Fig 4 Chimney connector ue collar with three 10 x 1 2 sheet metal screws Lift off the griddle and shield the stove s surface between the griddle opening and the...

Страница 8: ...above the replace opening Seal This Off ST243 thinble connection 12 13 99 djt Thimble Sleeve Chimney Connector Flue Keep sleeve end ush with ue tile ST243 Fig 6 The thimble made of either ceramic or...

Страница 9: ...NOT CONNECT THE DEFIANT TO ANY AIR DIS TRIBUTION DUCT OR SYSTEM ST245 fireplace flex connector 12 99 Flexible Connector Mantel Shield Fireplace Adapter Kit Positive Connection ST245 Fig 8 Through the...

Страница 10: ...De ant Costructional Hearth Dimensions as below At least 300 mm At least 150 mm or to a suitable heat resistant wall At least 150 mm Hearth Surface Free of Com bustible Material Perimeter should be c...

Страница 11: ...A Minimum distance from stove to movable combus tible materials e g furniture drying clothes etc 1220 mm 48 ST486a Defiant EU Clearance Diagrams 10 06 A B ST486a Fig 11 Minimum clearances D at least 3...

Страница 12: ...g the stove especially across rough surfaces can cause the legs to loosen or even break Storing the Handle Use the removable handle to open or close the doors After using it remove the handle so it wi...

Страница 13: ...ew to attach the damper handle to the damper stub on the left side Attach the Primary Air Thermostat Handle The primary air thermostat handle is the smaller of the two black handles Secure the handle...

Страница 14: ...e stove controls the amount of incoming air for starting maintaining and reviving a re More air entering the stove makes the re burn hotter and faster while less air prolongs the burn at a lower heat...

Страница 15: ...nd air dried outside under cover for at least one year If hardwood is not available you can burn softwoods that include tamarack yellow pine white pine East ern red cedar r and redwood These should al...

Страница 16: ...to get quite hot within a few minutes after a re is started the combus tor may stop working or the re may go out if the re dies down immediately as a result of the damper being closed Once the combus...

Страница 17: ...e it is in use 3 Light the newspaper and close the door Gradually build up the re by adding a few 76 127 mm 3 5 di ameter splits If this is one of the rst few break in res let the re burn brightly and...

Страница 18: ...sn t working Note that the catalyst is most likely to glow at its higher temperatures which it reaches when the rebox is in its lower range the catalyst is an after burner and the more waste fuel ther...

Страница 19: ...erial Return the ash pan to its original position in the stove and close and latch the ash door Fig 31 Do not operate the stove with the ash door open This will result in over ring and could cause dam...

Страница 20: ...the home An indoor chimney won t lose its heat to the outdoors so it takes less heat from the stove to heat it up and keep it warm Chimney Height The common wisdom tells us that a taller ue draws bet...

Страница 21: ...sture meters available for rewood you can also judge your wood by its appearance and weight If you get it green lift a piece and get a sense of its weight it can lose a third or more of its weight as...

Страница 22: ...crack a nearby window or door to enable the chimney to pull well that s a sign that you should install an outside air intake to bring combustion air directly to the stove An outside air adapter will a...

Страница 23: ...ss with water or a cleaner made espe cially for this purpose Do not use abrasive cleaners Use cleaning agents sparingly and be sure to keep them off the outer surfaces of the stove Rinse the glass tho...

Страница 24: ...he pressure screw from turning as you tighten the nut Re test the damper Tighten the Damper Handle as Needed A handle on the left side of the stove controls the damper The handle attaches to the dampe...

Страница 25: ...he stove damper and once again check the smoke leaving the chimney You should see signi cantly more smoke when the stove damper is open and exhaust does not pass through the combustor However be caref...

Страница 26: ...ing its effectiveness ST558 Inspect Catalytic element 4 11 00 Catalytic Ele ment Catalytic Access Panel ST558 Fig 38 Remove and inspect the catalytic element 5 Inspect the element for damage or degrad...

Страница 27: ...need periodic replacement The sizes of replaceable gasket are listed below along with their applications Gasket Diameter And the Parts it Seals 5 16 The griddle to the stove top wire reinforced gaske...

Страница 28: ...everyone out of the house Call the Fire Department Inspect the system every two weeks during the heat ing season as part of a regular maintenance schedule To inspect the chimney let the stove cool com...

Страница 29: ...alyst is still there it is covered or masked by the contaminant and cannot function To avoid this situation it is important not to burn any thing in your De ant that is a source of these contami nants...

Страница 30: ...roper clearance between chimney and nearby combustibles less than 51 mm 2 check local codes K Loose or leaky cleanout door For a replace F Improper clearance between smoke chamber and framing material...

Страница 31: ...9 85 86 87 70 78 71 88 59 90 52 91 91 CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time without notice De ant...

Страница 32: ...rt 1300642 58 Ashpan Bracket 30001908 59 Primary Air Valve Assy 5000024 60 Primary Air Frame3 1307411 61 Primary Air Rod3 1600058 62 Primary Air Valve3 1307412 63 Thermostat Handle Wood 1600660 64 Air...

Страница 33: ...0001612 1320621 30001616 Suede Brown 30002578 30002574 30002573 30002575 30002583 30002580 Vermont Classic Green 30002997 30002993 30002992 30002994 30002991 30002998 Shell Enamel Parts De ant Enamel...

Страница 34: ...34 Defiant Woodburning Stove 30003841...

Страница 35: ...te 3 Date of failure of catalyst 4 Any relevant information or circumstances regarding determina tion of failure 5 In addition the owner must return the failed catalyst Exclusions Limitations 1 This w...

Страница 36: ...CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: